• For R32 model, use pipes, 

fl

 are nut and tools which is speci

fi

 ed for R32 

refrigerant. Using of existing (R22) piping, 

fl

 are nut and tools may cause 

abnormally high pressure in the refrigerant cycle (piping), and possibly result in 

explosion and injury.

• Thickness of copper pipes used R32 must be more than 0.8 mm. Never use 

copper pipes thinner than 0.8 mm.

• Do not perform 

fl

 are connection inside a building or dwelling or room, when 

joining the heat exchanger of indoor unit with interconnection piping. Refrigerant 

connection inside a building or dwelling or room must be made by brazing or 

welding. Joint connection of indoor unit by 

fl

 aring method can only be made 

at outdoor or at outside of building or dwelling or room. Flare connection may 

cause gas leak and 

fl

 ammable atmosphere.

• After completion of installation or service, con

fi

 rm there is no leakage of 

refrigerant gas. It may generate toxic gas when the refrigerant contacts with 

fi

 re.

• Appliance and pipe-work shall be installed, operated and stored in a room with a 

fl

 oor area larger than A

min

 m

2

.

How to get A

min

 m

2

 : A

min

 = (M / (2.5 x 0.22759 x h

0

))

2

M is the refrigerant charge amount in appliance in kg. h

0

 is the installation height 

of the appliance in m: 0.6 m for 

fl

 oor standing/1.8 m for wall mounted/1.0 m 

for window mounted/2.2 m for ceiling mounted (For these units recommend 

installation height 1.0 m or less.).

• Comply with national gas regulations.

CAUTION

• Exposure of unit to water or other moisture before installation could result in 

electric shock.

Do not store it in a wet basement or expose to rain or water.

• After unpacking the unit, examine it carefully for possible damage.

• Do not install the unit at place where leakage of 

fl

 ammable gas may occur. In 

case gas leaks and accumulates at surrounding of the unit, it may cause of 

fi

 re.

• Do not install in a place that can increase the vibration of the unit. Do not 

install in a place that can amplify the noise level of the unit or where noise and 

discharged air might disturb neighbors.

• To avoid personal injury, be careful when handling parts with sharp edges.

• Please read this installation manual carefully before installing the unit. It contains 

further important instructions for proper installation.

• The manufacturer shall not assume any liability for the damage caused by not 

observing the description of this manual.

EN

ES

FR

IT

PT

PL

CZ

RU

CR

HU

TR

NL

GR

SV

FI

NO

DK

RO

BG

EE

LV

SK

SI

DE

3

Содержание RAS-B10U2FVG-E

Страница 1: ...AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL Indoor unit RAS B10 13 18U2FVG E R32 1112151199 ...

Страница 2: ...tallation Parts 6 INDOOR UNIT 7 Installation Place 7 Cutting a Hole and Mounting Installation Plate 7 How to Install Indoor Unit 8 Concealed Installation 9 OTHERS 10 Gas Leak Test 10 Setting of Remote Control Selector Switch 10 Remote Control A B Selection 10 Test Operation 10 Auto Restart Setting 10 EN ...

Страница 3: ...e of appliance use shall be at least polychloroprene sheathed flexible cord design H07RN F or cord designation 60245 IEC66 Shall be installed in accordance with national wiring regulations CAUTION This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm in all poles DANGER FOR USE BY QUALIFIED PERSONS ONLY TURN O...

Страница 4: ...ght of the unit Personal injury and property damage can result if the unit falls Before doing the electrical work attach an approved plug to the power supply cord Also make sure the equipment is properly earthed Appliance shall be installed in accordance with national wiring regulations If you detect any damage do not install the unit Contact your dealer immediately Do not use any refrigerant diff...

Страница 5: ... is the refrigerant charge amount in appliance in kg h0 is the installation height of the appliance in m 0 6 m for floor standing 1 8 m for wall mounted 1 0 m for window mounted 2 2 m for ceiling mounted For these units recommend installation height 1 0 m or less Comply with national gas regulations CAUTION Exposure of unit to water or other moisture before installation could result in electric sh...

Страница 6: ...ation is not accepted by the supplier the service agency will take adequate countermeasures Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type R32 GWP 1 value 675 ex R32 ref AR4 1 GWP global warming potential The refrigerant quantity is indicated on the unit name plate This value is based on...

Страница 7: ...ille Filter Maintenance Shelf life Clean every 3 6 months when dust tuck or covers the filter 1 Recommend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use the plain water to wash the filter dry with the sunlight for 3 4 hours or until it completely dry Nevert...

Страница 8: ...ol holder Do not allow the drain hose to get slack Make sure to run the drain hose sloped downward The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Insulate the refrigerant pipes separately with insulation not together 8 mm thick heat resisting polyethylene foam Cut the piping hole sloped slightly Right Rear right Left Bottom right Rear left ...

Страница 9: ...hole brim ring sold separately A place which provides the spaces around the indoor unit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened In case of block brick concrete or similar type walls make 5 mm holes in the wall Insert clip anch...

Страница 10: ... Do not form the drain hose into a wavy shape Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch Drainage 1 Run the drain hose sloped downwards Wiring connection Wiring of the connection cable is necessary to remove the front panel 1 Remove the terminal cover and cord clamp 2 Insert the connecting cable according to the local rule into the pipe hole on the...

Страница 11: ...or more 20 to 30 240 to 250 Floor Wall Side view Unit mm 4 In case of lattice establishment Follow the following figure make sure to keep enough distance between lattice frame and wall Be sure to switch to wall burying mode The lattice should be make of wood Between the air inlet and outlet should be devided with partition board Be sure to establish the open part for RECEIVER The open part of latt...

Страница 12: ...y Remote Control B Setup 1 Push and hold button on the Remote Control by the tip of the pencil 00 will be shown on the display Picture 1 2 Press during pushing B will show on the display and 00 will disappear and the air conditioner will turn OFF The Remote Control B is memorized Picture 2 Note 1 Repeat above step to reset Remote Control to be A 2 Remote Control A has not A display 3 Default setti...

Страница 13: ...1112151199 ...

Отзывы: