– 22 –
Outdoor Unit : RAS-4M27YAV-E
<Heating>
System
Compressor
Fan motor FLA
Voltage range
Power supply
Combination of
indoor unit operation
Hz
Volts-
Ph.
Min.
Max.
MCA
ICF
MOCP
(Amps)
MSC
RLA
Indoor
Outdoor
10
–
–
–
7.88
7.88
20
5.78
5.78
0.15 x 1 = 0.15
0.5
13
–
–
–
11.20
11.20
20
8.44
8.44
0.15 x 1 = 0.15
0.5
1 unit
16
–
–
–
13.15
13.15
20
10.00
10.00
0.15 x 1 = 0.15
0.5
10
10
–
–
11.45
11.45
20
8.52
8.52
0.15 x 2 = 0.30
0.5
13
10
–
–
12.66
12.66
20
9.49
9.49
0.15 x 2 = 0.30
0.5
16
10
–
–
13.55
13.55
20
10.20
10.20
0.15 x 2 = 0.30
0.5
13
13
–
–
13.55
13.55
20
10.20
10.20
0.15 x 2 = 0.30
0.5
16
13
–
–
14.78
14.78
20
11.18
11.18
0.15 x 2 = 0.30
0.5
2 units
16
16
–
–
15.66
15.66
20
11.89
11.89
0.15 x 2 = 0.30
0.5
10
10
10
–
12.51
12.51
20
9.25
9.25
0.15 x 3 = 0.45
0.5
13
10
10
–
12.80
12.80
20
9.48
9.48
0.15 x 3 = 0.45
0.5
16
10
10
–
12.80
12.80
20
9.48
9.48
0.15 x 3 = 0.45
0.5
13
13
10
–
12.80
12.80
20
9.48
9.48
0.15 x 3 = 0.45
0.5
16
13
10
–
13.08
13.08
20
9.70
9.70
0.15 x 3 = 0.45
0.5
13
13
13
–
13.08
13.08
20
9.70
9.70
0.15 x 3 = 0.45
0.5
16
16
10
–
13.35
13.35
20
9.92
9.92
0.15 x 3 = 0.45
0.5
16
13
13
–
13.35
13.35
20
9.92
9.92
0.15 x 3 = 0.45
0.5
16
16
13
–
13.35
13.35
20
9.92
9.92
0.15 x 3 = 0.45
0.5
3 units
16
16
16
–
13.63
13.63
20
10.14
10.14
0.15 x 3 = 0.45
0.5
10
10
10
10
11.38
11.38
20
8.22
8.22
0.15 x 4 = 0.60
0.5
13
10
10
10
11.38
11.38
20
8.22
8.22
0.15 x 4 = 0.60
0.5
16
10
10
10
12.20
12.20
20
8.88
8.88
0.15 x 4 = 0.60
0.5
13
13
10
10
12.20
12.20
20
8.88
8.88
0.15 x 4 = 0.60
0.5
16
13
10
10
12.20
12.20
20
8.88
8.88
0.15 x 4 = 0.60
0.5
13
13
13
10
12.20
12.20
20
8.88
8.88
0.15 x 4 = 0.60
0.5
16
13
13
10
12.20
12.20
20
8.88
8.88
0.15 x 4 = 0.60
0.5
13
13
13
13
12.20
12.20
20
8.88
8.88
0.15 x 4 = 0.60
0.5
4 units
16
16
10
10
50 or 60
230–1
198
264
12.20
12.20
20
8.88
8.88
0.15 x 4 = 0.60
0.5
NOTE :
Model of Indoor unit 10 : RAS-M10YKV-E, 13 : RAS-M13YKV-E, 16 : RAS-M16YKV-E
MCA : Minimum Circuit Amps.
ICF
: Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)
MOCP : Maximum Overcurrent Protection (Fuse only)
MSC : Maximum Starting Current
FLA
: Full Load Amps.
RLA
: Rated Load Amps. RLA under conditions on the right.
DB
WB
Indoor temp.
(°C)
20
—
Outdoor temp. (°C)
7
6