– 76 –
10. INSTALLATION PROCEDURE
10-1. Safety Cautions
2 m
or more
Air filters
Connecting
cable
[Z] Shield pipe
(for extension drain hose)
The indoor unit shall be installed
so that the top of the indoor unit
is positioned at least 2 m high.
Also, avoid putting anything
on the top of the indoor unit.
For the rear left and left piping
Before installing the wireless remote controller
• With the remote controller cover removed,
correctly load the supplied batteries while observing their polarity.
Insulate the refrigerant pipes
separately, not together.
The auxiliary piping can be
connected at the left, rear left,
rear right, right, bottom right
or bottom left as shown below.
Make sure the drain hose is
sloped downward.
Do not allow the drain hose
to become slack.
Insert the cushion between
the indoor unit and wall, and
tilt the indoor unit for better
installation work.
Wall
Cut the piping hole
slightly sloped
Right
Rear right
Bottom right
Rear left
Bottom left
Left
8 mm thick heat resisting
polyethylene foam
Hook
Hook
Hook
Hook
70 mm or more
160 mm or more
180 mm
or more
[1] Installation plate
[5] Mounting screw
[2] Wireless remote controller
When installing the outdoor unit,
leave open in at least two of directions
(A), (B), (C) and (D) shown in the right figure.
As shown in the figure,
position power cord and
connecting cable downward,
and lead out along piping
connection port.
80 mm or more only when unobstructed
to the front and both sides.
In principle,
leave open
50 mm or more
from wall
100 mm or more
from wall
200 mm or more
Ensure sufficient space
to allow drainage
(A)
[Y]
(D)
(C)
(B)
Connecting cable
Extension drain hose
Power cord
250 mm or more
from wall
[2] Wireless
remote
controller
[4] Remote controller
holder
[6] Remote controller holder
mounting
screw
CAUTION
Install in rooms that are 5 m³ or larger.
If a leak of refrigerant gas occurs inside the room,
an oxygen deficiency can occur.
[3] Batteries
Cover
• If the system will be used in cooling mode when the outdoor temperature is below zero, take measures to
ensure that the drain water does not freeze.
• When the outdoor unit is installed in a place that is always exposed to strong winds like on the coast or on a
high story of a building, secure the normal fan operation using a duct or a wind shield.