Item
Operation flow and applicable data, etc.
Description
2
4
. Short Timer
In the normal condition, after switching one circuit
breaker, 3-minute delay time for compressor and
1 hour for plasma air purifier are set for the
maintenance of the unit.
Purpose
To start the unit immediately for the purpose of
testing, trial...etc, short timer can be used.
maintenance of the unit.
Short Timer Setting
purifier on the remote control without
j
Press [ ] button to turn the unit OFF.
k
Set the operation mode or plasma air
sending the signal to the unit.
l
Pre
ss
button and hold, "00" will
show
on display, them press [
]
button
to make "00" disappear.
m
Press [ ] button to turn the unit ON.
n
When short timer is activated, all
setting on the remote operates
immediately, besides, all indicatiors on
front panel turns ON continuously for
3 seconds.
FIX
MODE
FAN
MENU
FIX
4
3
FIX
2
5
.
Cord
Heater
Control
2.
1. Purpose
Base plate freeze prevention of the
outdoor unit.
Operation
As shown in the figure below, the
base plate freeze preventive
heater is controlled by temperature
of the outside temperature sensor
(TO).
B
ase plate cord heater control
When TO sensor is defective or the air
conditioner is cooling operation, heater
output is turned off.
TO temp.
Heater output
OFF
2ºC
0 ºC
ON
(Equivalent to 100W)
- 46 -