background image

(A)

(B)

(C)

(D)

Vinyl tape
Apply after carrying
out a drainage test.

600 mm or more only
when unobstructed
to the front and both
sides.

Extension 
drain hose
(Not available, 
provided by installer)

100 mm or more

100 mm or 

more

600 mm or more

600 mm or more

Saddle

1

  Installation plate

50 mm or more

50 mm or more

Shield pipe

Air fi lter

5

 Filter

6

 Filter

70 mm or more

Toshiba 1112150201 (EN)

INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS

Part

code

Parts name

Q’ty

A

Refrigerant piping
Liquid side  : 

6.35 mm

Gas side 

9.52 mm

 

  (RAS-(B) 10, 13UFV Series)

 

12.7 mm

 

  (RAS-(B) 18UFV Series)

One

each

B

Pipe insulating material
(polyethylene foam, 8 mm thick)

1

C

Putty, PVC tapes

One

each

Optional Installation Parts

  Secure the outdoor unit with fi xing bolts and nuts if the unit is likely to be exposed 

to a strong wind.

  Use 

8 mm or 

10 mm anchor bolts and nuts. 

  If it is necessary to drain the defrost water, attach drain nipple and cap water proof 

to the bottom plate of the outdoor unit before installing it.

Fixing bolt arrangement of outdoor unit

RAS-10, 13, 18SAV Series

3

 Batteries

8

  Pan head 

wood screw

4

 Remote control holder

Remark :

• 

Detail of accessory and installation 
parts can see in the accessory sheet.

When installing the outdoor unit, 
leave open in at least two of direction 
(A), (B), (C) and (D) shown in the 
fi gure on the right.

Do not allow the drain hose to get 
slack.

Make sure to run the drain hose 
sloped downward.

The auxiliary piping can be 
connected to the left, rear left, rear 
right, right, bottom right or bottom 
left.

Insulate the refrigerant pipes 
separately with insulation, not 
together.

8 mm thick heat resisting
polyethylene foam

Cut the piping 
hole sloped 
slightly.

Right

Rear right 

Left

Bottom right 

Rear left

Bottom left

Cut dot-line area

In case of right or left piping

*  Drain nipple and cap 

water proof are packed 
in outdoor unit.

When using a multi-system outdoor unit is used, refer to the installation manual 
provided with the model concerned.

Air outlet

Drain outlet

Air inlet

108 mm

600 mm

28 mm

25 mm

9

0 mm

125 mm

320 mm

86 mm

102 mm

 CAUTION 

Install in rooms that are 13 m

3

 or larger. 

If a leak of refrigerator gas occurs 
inside the room, an oxygen defi ciency 
can occur.

7

 Mounting screw

9

 Insulation sheet

2

  Wireless remote control

3

Содержание RAS-18SAV Series

Страница 1: ...V E RAS 3M18SAV E RAS 3M26GAV E1 RAS 4M23SAV E RAS 4M27GAV E1 RAS 5M34UAV E AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH ESPAÑOL FRANÇAIS ITALIANO DEUTSCH PORTUGUÊS POLSKI ČESKY PУCСКИЙ HRVATSKI MAGYAR TÜRKÇE NEDERLANDS ΕΛΛΗΝΙΚΑ SVENSKA SUOMI NORSK DANSK ROMÂNĂ БЪЛГАРСКИ EESTI LATVISKI SLOVENČINA SLOVENŠČINA ...

Страница 2: ... Łączenie Instalacji Rurowej Czynnika Chłodniczego 7 Usuwanie Powietrza 8 Podłączenie Okablowania 8 Prace Elektryczne 8 INNE 9 Próba Gazoszczelności 9 Ustawianie Przełącznika Wyboru Pilota 9 Ustawienia Przełącznika A B Wyboru Pilota 9 Próba Działania 9 Włączanie Funkcji Automatycznego Wznawiania Pracy Auto Restart 9 PL OBSAH BEZPEČNOSTNÍ OPATŘENÍ 1 SCHÉMA INSTALACE VNITŘNÍ A VENKOVNÍ JEDNOTKY 3 Vo...

Страница 3: ...TE INTERIOARĂ 4 Locul de Instalare 4 Executarea unei Găuri şi Montarea Plăcii de Instalare 4 Cum se Instalează Unitatea Interioară 5 Instalarea Mascată 6 UNITATEA EXTERIOARĂ 7 Locul de Instalare 7 Măsuri de Precauţie privind Instalarea în Regiuni cu ninsori Abundente şi Temperaturi Scăzute 7 Drenarea Apei din Unitatea Exterioară 7 Racordarea Ţevilor de lichid Refrigerent 7 Evacuarea 8 Racordarea C...

Страница 4: ...s of charging port connecting sections on the main unit are different from those for the conventional refrigerant and different size tools are also required For connecting pipes use new and clean piping materials with highpressure withstand capabilities designed for R410A only and ensure that water or dust does not enter Moreover do not use any existing piping as its pressure withstand may be insu...

Страница 5: ... unit is not enough or installation of the unit is improper the unit may fall and result in injury Electrical work must be performed by a qualified electrical engineer in accordance with the code governing such installation work internal wiring regulations and the manual A dedicated circuit and the rated voltage must be used Insufficient power supply or improper installation may cause electrical s...

Страница 6: ...r unit RAS 10 13 18SAV Series 3 Batteries 8 Pan head wood screw 4 Remote control holder Remark Detail of accessory and installation parts can see in the accessory sheet When installing the outdoor unit leave open in at least two of direction A B C and D shown in the figure on the right Do not allow the drain hose to get slack Make sure to run the drain hose sloped downward The auxiliary piping can...

Страница 7: ...pipe hole brim ring sold separately A place which provides the spaces around the indoor unit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened In case of block brick concrete or similar type walls make 5 mm holes in the wall Insert clip...

Страница 8: ... drain hose Do not form the drain hose into a wavy shape Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch Drainage 1 Run the drain hose sloped downwards Wiring connection Wiring of the connection cable is necessary to remove the front panel 1 Remove the terminal cover and cord clamp 2 Insert the connecting cable according to the local rule into the pipe ...

Страница 9: ... Floor 670 or more 20 to 30 240 to 250 Floor Wall Side view Unit mm 4 In case of lattice establishment Follow the following figure make sure to keep enough distance between lattice frame and wall Be sure to switch to wall burying mode The lattice should be make of wood Between the air inlet and outlet should be devided with partition board Be sure to establish the open part for RECEIVER The open p...

Страница 10: ...aces A place full of machine oil A saline place such as the coast A place full of sulfide gas A place where high frequency waves are likely to be generated such as from audio equipment welders and medical equipment Strong wind Snow protection plate Snow protection hood At least 50 cm Snow accumulation line Holding frame Front Anchor bolts Install at least 50 cm above the snow accumulation line Do ...

Страница 11: ... valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves VACUUMING Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump Do not use the refrigerant in the outdoor unit For details see the manual of the vacuum pump Tightening torque for connection ...

Страница 12: ...ton on the Remote Control by the tip of the pencil 00 will be shown on the display 2 Press during pushing B will show on the display and 00 will disappear and the air conditioner will turn OFF The Remote Control B is memorized Note 1 Repeat above step to reset Remote Control to be A 2 Remote Control A has not A display 3 Default setting of Remote Control from factory is A Unit B setup Press and ho...

Отзывы: