– 5 –
FILE NO. SVM-05016
Note : 1
•
Capacity is based on the following temperature conditions.
Note : 2
•
Charge refrigerant according to the table below.
RAS-24
N
KH
D
-E
4
/ RAS-24UAH-E
4
RAS-18
N
KH
D
-E
4
/ RAS-18UAH-E
4
RAS-24
N
K
D
-E
4
/ RAS-24UA-E
4
RAS-18
N
K
D
-E
4
/ RAS-18UA-E
4
Refrigerant RAS-24
N
K
D
X
4
/ RAS-24UAX
4
RAS-18
N
K
D
X
4
/ RAS-18UAX
4
RAS-24
N
K
D
-AR
4
/ RAS-24UA-AR
4
RAS-18
N
K
D
-AR
4
/ RAS-18UA-AR
4
RAS-24
N
K
D
X
4
-T / RAS-24UAX
3
-T
1
RAS-18
N
K
D
X
4
-T
2
/ RAS-18UAX
4
-T
2
1 No need to charge
15 m or less
15 m or less
extra refrigerant
2 Need to charge
Over 15 m up to 25 m (30 g/m) Over 15 m up to 20 m (20 g/m)
extra refrigerant
Temperature
Condition
JIS B8615-1
Cooling
Heating
Indoor unit inlet air temperature
(DB)
27°C
20°C
(WB) 19°C 15°C
Outdoor unit inlet air temperature
(DB)
35°C
7°C
(WB)
24°C
6°C