Item
Operation flow and applicable data, etc.
Description
8. Louver control
•
Swing operation is perfor in range 35° with the Fixed position as
the center.
•
If the swing range exceeded either upper or lower limit position,
swing operation is perfomed in range 35° from the limit.
3) Swing
•
Fixed
Position
before start
swing
Upper Limit
Position.
Lower Limit
Position
30
o
5
o
Swing
range 35
o
Swing
When pressing
[SWING] button during
operation, the louver
starts swinging.
Upper Limit
Position.
Lower Limit
Position.
Fixed Position
before start
swing.
17.5
o
17.5
o
Swing
range 35
o
•
Up-Down and Left-Right
louver are same setting.
4) HADA CARE
Position
•
Air flow upward to the ceiling provide indirect air flow to body
and homogenize room temperature.
•
HADA care Louver position.
Initial setting of "Cooling storage position"
Louver : Directs downward (33.9°)
Heating operation/
AUTO (HEAT)
Initial setting of “Heating storage position”
Louver : Directs downward (79.1°)
Cooling operation/
AUTO (COOL)
- 45 -