8-1-8. Outdoor fan control (DC fan motor)
Although the outdoor fan motor drives the outdoor fan by non-step variable system of the revolution speed, the
revolution speed is restricted to three steps on the convenience of controlling. If a strong wind is lashing outside
of the room, the operation may be continued as the outdoor fan stops in order to protect the outdoor fan motor.
If a fan lock occurred due to entering of foreign matter, the air conditioner stops and an alarm is displayed.
<COOL, DRY>
Table 8-1-3
<HEAT>
Table 8-1-4
Model name
RAS-13UAV-E2
Compressor revolution (rps)
To 16.8
To 57.4
From 58.0
Outdoor temp. sensor TO
TO
≥
5
°
C
390
650
840
TO
<
5
°
C
650
650
840
ECONO. operation
TO
≥
5
°
C
390
390
650
TO
<
5
°
C
390
650
650
TO is abnormal
390
650
840
Model name
RAS-13UAV-E2
Compressor revolution (rps)
To 13.8
To 34.7
From 35.3
TO
≥
38
°
C
390
840
840
Outdoor temp. sensor TO
TO
<
38
°
C
390
700
840
TO < 15
°
C
390
TO
≥
38
°
C
390
700
840
ECONO. operation
TO
<
38
°
C
390
390
700
TO
<
15
°
C
390
TO is abnormal
700
700
840