– 13 –
7-2-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the
desired position.
And the louver position is stored in the microcom-
puter, the louvers will be set to the position auto-
matically at the next operation.
(2) When the AUTO button is pushed, the louver ver-
tically swings within range of 25deg.
7-3. DRY Operation
(MODE of the remote control : DRY)
(1) Compressor, outdoor fan and operation display are
controlled as shown in Fig. 7-3-1.
Fig. 7-3-1
•
The microprocessor turns the compressor on
and off at regular intervals (4 to 6 minutes on
and/or off). During the compressor off, the in-
door fan will operate in the super low position.
•
The indoor fan will operate in the AUTO posi-
tion.
(2) The pattern of operation depending on the rela-
tion between room temperature and set tempera-
ture is shown below:
Room temp.
Set temp.+1
Set temp.
Compressor
Outdoor fan
Indoor fan
L.
*
S.L.
S.L.
L.
L.
S.L.
L.
ON
ON
ON
ON
OFF
OFF
OFF
*
Super Low
Fig. 7-3-2
(Room temp. – Set temp.)
Set
temp.
ON
+3
+2
+1
0
OFF
OPERATION
display
Compressor Outdoor fan
(RY01)
Common relay
(RY02)
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
ON
Содержание RAS-13SA-E
Страница 46: ... 46 9 4 2 PC Board Layout Bottom View Top View ...
Страница 56: ......