background image

 

 

 

 

 

For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192  
 

Page: 4 of 6 

 

 

Setting the Setpoint 

The setpoint is adjusted according to whatever level is necessary to yield the desired process 
variable setting.  The setpoint will be entered as a frequency (Hz) value and not as the process 
variable’s value (PSI, temperature, etc.).  It is entered as a frequency because the setpoint is related 
as a percentage of the feedback signal.  For example, if the transducer’s measurement range is 0 to 
300 PSI and the target is 150 PSI, the setpoint should be set at 50% of the Upper Limit Frequency.  If 
the Upper Limit Frequency is 60 Hz, the setpoint would be 30 Hz. 
 
The setpoint is set by the commanded frequency.  The frequency command is determined by the 
Frequency Mode Selection 1 (F004).  The settings for Frequency Mode Selection 1 can be seen 
below. 
 

Direct 

Access 

Parameter Name 

Settings 

Default
Setting

 
 
 
 
 

F004 

 
 
 
 
 
Frequency Mode Selection 1 

1: V/I 
2: RR 
3: RX 
4: Panel Keypad 
5: RS485 (2-wire) 
6: RS485 (4-wire) 
7: Communication Option Board 
8: RX2 
9: Option V/I 
10: Up/Down Frequency 
11: Pulse Input (option) 
12: Pulse Input (motor CPU) 
13: Binary/BCD Input (option) 

 
 
 
 
 

2: RR 

 
It is important not to set Frequency Mode Selection 1 (F004) the same as the PID Feedback Signal 
Selection (F360) as this will change the setpoint as the process variable changes and will cause 
unfavorable results.  In most cases, the Frequency Mode is set from the Electronic Operator Interface 
(EOI).  Setting F004 to “4: Panel Keypad” will use the EOI to set the setpoint.  However, the user may 
use any of the settings listed above to set the setpoint. 
 

Determining the Setpoint 

The range of the transducer must be known to accurately calculate the setpoint.  The following 
equation is used to calculate the setpoint: 
 

ASD Setpoint

 

Limit

Upper

mA

at

units

mA

at

units

units

setpt

desired

_

4

_

_

20

_

_

_

_





 

 

 
 

Содержание Q9 HVAC

Страница 1: ...peed of the motor fan to maintain a constant static pressure in the ductwork As the dampers on the output side of the fan are opened the static pressure in the system will begin to drop The drive senses this change in static pressure via a 4 20mA feedback signal and the drive will increase the speed of the motor fan to bring the static pressure to the desired level Conversely the drive will slow t...

Страница 2: ...al Because the V I terminal is an isolated analog input and the transducer is powered from P24 the current loop will not be complete A jumper will need to be placed between CC and IICC to make the V I terminal non isolated 4 Wire A 4 wire transducer is powered from an external source and does not use the drive for power Two of the wires will connect to the external power source The feedback signal...

Страница 3: ... 00 2 55 0 00 F367 Process Upper Limit Lower Limit Upper Limit 60 00 Hz F368 Process Lower Limit Lower Limit Upper Limit 0 00 Hz F369 PID Control Wait Time 0 2400 sec 0 sec F370 PID Output Upper Limit Lower Limit Upper Limit 60 00 Hz F371 PID Output Lower Limit Lower Limit Upper Limit 4 00 Hz F372 Process Increasing Rate 0 1 600 0 sec 10 0 sec F373 Process Decreasing Rate 0 1 600 0 sec 10 0 sec En...

Страница 4: ...quency Mode Selection 1 can be seen below Direct Access Parameter Name Settings Default Setting F004 Frequency Mode Selection 1 1 V I 2 RR 3 RX 4 Panel Keypad 5 RS485 2 wire 6 RS485 4 wire 7 Communication Option Board 8 RX2 9 Option V I 10 Up Down Frequency 11 Pulse Input option 12 Pulse Input motor CPU 13 Binary BCD Input option 2 RR It is important not to set Frequency Mode Selection 1 F004 the ...

Страница 5: ...te the setpoint on a pressure control system with the following transducer characteristics Pressure Transducer Range 0 300 PSI Transducer Output 4 20 mA Desired Pressure 60 PSI ASD Setpoint Hz PSI PSI PSI 60 0 300 60 ASD Setpoint 12 Hz Examples Note These values are starting point suggestions for tuning They may or may not get the desired result right away ...

Страница 6: ...shiba Adjustable Speed Drive Marketing Dept at 800 872 2192 Page 6 of 6 Revision History Rev Date Written Revised By Approved By Description 1 1 6 23 2011 Joshua Austin Terry Voigt Formatting Revised to incorporate document control requirements ...

Отзывы: