For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
Page: 3 of 6
Programming
Below are the adjustable PID parameters and their default settings.
Direct
Access
Parameter Name
Range
Default
Setting
F359
PID Control Switching
0: PID Off
1: Process PID
2: Speed PID
0
F360
PID Feedback Signal Selection
0: Feedback Value = 0
1: V/I
2: RR
3: RX
4: RX2
5: Option V/I
6: PG Feedback
0
F361
PID Feedback Delay Filter
0.0 – 25.0
0.0
F362
PID Feedback Proportional (P) Gain
0.0 – 100.0
0.10
F363
PID Feedback Integral (I) Gain
0.01 – 100.00
0.10
F354
PID Deviation Upper Limit
0.00 – 60.0 Hz
60.00 Hz
F365
PID Deviation Lower Limit
0.00 – 60.00 Hz
60.00 Hz
F366
PID Feedback Differential (D) Gain
0.00 – 2.55
0.00
F367
Process Upper Limit
Lower Limit – Upper Limit
60.00 Hz
F368
Process Lower Limit
Lower Limit – Upper Limit
0.00 Hz
F369
PID Control Wait Time
0 – 2400 sec
0 sec
F370
PID Output Upper Limit
Lower Limit – Upper Limit
60.00 Hz
F371
PID Output Lower Limit
Lower Limit – Upper Limit
4.00 Hz
F372
Process Increasing Rate
0.1 – 600.0 sec
10.0 sec
F373
Process Decreasing Rate
0.1 – 600.0 sec
10.0 sec
Enabling Process PID Control (F359)
To operate the Q9 in Process PID mode, Parameter F359 (PID Control Switching) must be set to “1:
Process PID”.
PID Feedback Signal Selection (F360)
A feedback signal from a transducer needs to be sent to the drive in order for PID control to function
properly. The type of signal being used to measure the system variable determines what the value of
Parameter F360 should be set to. In most cases, the feedback signal from the transducer is a 4-20
mA signal and F360 should be set to “1: V/I”.