64
PROSEC T3H
2. Expanded Functions
Inside the parameter (cont’d):
Status S20LP
Ethernet
Abn
0: Normal complete
1: Error complete
Busy
0: Initial state
1: Transmission port busy
Status
0: Initial state
1: While send requesting
2: While waiting response
3: Complete
TermSTS
H00: Normal complete
H01: Register designation error
H02: Response time-out
H03: Parameter error
H04: Register write protect
H05: (Reserve)
H06: Module error (send time-out)
H07: No send channel
H08: Invalid station No.
H09: Transfer size error
H0A: Boundary error
H0B: Transmission error
Bit 7 indicates the error is occurred
H0C: I/O no answer error
whether self-station or target-station.
H0D: IC card designation error
0: Self-station
H0E: (Reserve)
1: Target-station
H0F: (Reserve)
Transmission error
information
When TermSTS is H0B, the error information is stored. (0 for other cases)
For detailed information, refer to the S20LP or EN311 manual.
Example
RW010
2
1
3
S20LP, channel 1, target station No. is 3
RW011 0
RW012
128
Transfer size: 128 words
RW013
3
Self-station RW register
RW014
100
Leading address: RW100
RW015
4
Target-station D register
RW016
1000
Leading address: D1000
RW017
10
Response time limit: 1 second
Send
requesting
RW050 0 0 1
0
0
RW051 0