6F3B0250
218
T1/T1S User’s Manual
7. Instructions
FUN 120
ENC
Encode
Expression
Input
-
[
A
ENC (
n
)
B
]
-
Output
Function
When the input is ON, this instruction finds the bit position of the most significant ON bit in the bit table,
size 2
n
bits starting with 0 bit (LSB) of
A, and stores it in B.
Execution condition
Input
Operation
Output
ERF
OFF
No execution
OFF
-
ON
Normal execution
ON
-
There is no ON bit (no execution)
OFF
Set
Operand
Name
Device
Register
Constant Index
X
Y
R
S
T.
C. XW YW RW SW
T
C
D
I
J
K
A
Start of table
Ö
Ö
Ö
Ö
Ö
Ö
Ö
n
Table size
1 - 8
B
Encode result
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Example
2
5
(=32) bits starting with 0 bit of RW05 (R050 to R06F) are defined as the bit table.
When R010 is ON, the most significant ON (1) bit position in the bit table is searched, and the
position is stored in D0010.
The following figure shows an operation example.
RW06
RW05
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9
3
2
1
0
0 0 0 0 0 1 0 0 1 0 0 1 1 0 0 0 0 1 1 1 0 1 0
0 0 1 0
D0010
26
Note
·
If there is no ON bit in the bit table, the instruction error flag (ERF = S051) is set to ON.