E6581738
- 17 -
3.6.1.
Examples of reading the PROFIdrive parameter
3.6.1.1. Example 1. Reading the PNU 922 (Telegram)
AK = 1 (Request parameter value)
SPM = 0
PNU = 922 (0x039A)
PKE
0 0 0 1 0 0 1 1 1 0 0 1 1 0 1 0
1 3 9 A
Requirement
PKW PZD
PKE IND PWE
13 9A
00 00 00 00 00 00
・・・
・・・
Response (Value: 0x0065 = 101)
13 9A
00 00 00 00 00 65
・・・
・・・
3.6.1.2. Example 2. Reading the PNU 964, IND 0
AK = 6 (Request parameter value (array))
SPM = 0
PNU = 964 (0x03C4)
IND = 0 (PDP003Z ID)
PKE
0 1 1 0 0 0 1 1 1 1 0 0 0 1 0 0
6 3 C 4
Requirement
PKW PZD
PKE IND PWE
63 C4 00 00
00 00 00 00
・・・
・・・
Response (Value: 0x0C24 = PDP003Z ID)
43 C4 00 00
00 00
0C 24
・・・
・・・