E6581738
- 16 -
3.6.
PROFIBUS parameter (PNU)
PNU R/W
data
type
Note
915 R
Array
[6]
Unsigned16
PNU 915, IND 0 = the
drive
parameter
c001
PNU 915, IND 1 = the
drive
parameter
c002
PNU 915, IND 2 = the
drive
parameter
c003
PNU 915, IND 3 = the
drive
parameter
c004
PNU 915, IND 4 = the
drive
parameter
c005
PNU 915, IND 5 = the
drive
parameter
c006
916 R
Array
[6]
Unsigned16
PNU 916, IND 0 = the
drive
parameter
c021
PNU 916, IND 1 = the
drive
parameter
c022
PNU 916, IND 2 = the
drive
parameter
c023
PNU 916, IND 3 = the
drive
parameter
c024
PNU 916, IND 4 = the
drive
parameter
c025
PNU 916, IND 5 = the
drive
parameter
c026
918 R
Unsigned16
Station
address monitor (same as the
drive
parameter
c150
).
922 R
Unsigned16
Telegram
selection
1, 100, 101, 102
927 R/W
Unsigned16
Operator
control rights (parameter identification, PKW).
Value
: Mode
0
:
Parameters cannot be written, only read
(927 can be written).
1: Parameters can be written and read (default).
928
R
Unsigned16
Control rights (process data, PZD).
1: PZD part is enabled.
930 R
Unsigned16
Operating mode
1
:
supports the speed control mode and the speed
setpoint channel comprises RFG functionality.
944 R
Unsigned16
Fault message counter
947 R
Array
[1]
Unsigned16
Fault number
963
R
Unsigned16
Detected baud rate:
0 = 9.6 kbit/s
1 = 19.2 kbit/s
2 = 93.75 kbit/s
3 = 187.5 kbit/s
4 = 500 kbit/s
6 = 1.5 Mbit/s
7 =
3 Mbit/s
8 =
6 Mbit/s
9 = 12 Mbit/s
964 R
Array [5]
Unsigned16
Drive Unit identification
IND 0 = PDP003Z ID (0x0C24)
IND 1 = Manufacturer-ID (0x0190)
IND 2 = VF-MB1/S15 CPU1 version
IND 3 = VF-MB1/S15 firmware release year (yyyy)
IND 4 = VF-MB1/S15 firmware release date (ddmm)
965
R
Octet String2
Profile number of the
PDP003Z
(Profidrive, V4.1)