background image

ISOLATED-REDUNDANT UPS SYSTEMS

*UPSISOREDUNDNT060301*

UPS    ADJUSTABLE SPEED DRIVES    MOTORS    CONTROLS   INSTRUMENTATION     PLC

 

INDUSTRIAL DIVISION

13131 West Little York Road, Houston, Texas 77041

Tel (713)466-0277   Fax (713)892-5212

US (800)231-1412   Canada (800)872-2192   Mexico 01(800)527-1204

www.toshiba.com/ind

Copyright 3/2006  

Available Through:

Isolated-Redundant UPS Module

Oversized Redundant UPS Module

Toshiba’s 

Isolated 

Redundant 

UPS 

System  offers  the  ultimate  in  reliability, 
maintainability  and  availability.    This  UPS 
system delivers maximum design flexibility 
that is unmatched by any other configured 
UPS design.  

An isolated-redundant UPS system allows 
the  user  to 

never

  have  critical  loads 

exposed or fed from the utility source, even 
during UPS module failures or UPS module 
maintenance.    The  principal  behind  this 
system  is  that  the  critical  load  is  divided 
into  separated,  isolated  segments,  which 
means  that 

the  failure  of  one  segment 

cannot  affect  the  other  load  segments

.  

Reliability  is  maximized  and  common-
mode failure is minimized!  

Each load segment can be a single, modular 
UPS system.  If a UPS load segment failure 
causes  a  transfer  to  static  bypass,  the 
static  bypass  source  is 

another  standby 

UPS system.

In  isolated  redundant  systems,  the 
standby  UPS  system  is  always  ready  to 
support the critical load since it is on-line 
and  keeps  its  own  battery  plant  charged.   
A key requirement of this system is that the 
standby  UPS  system  must  accept  a  100%  step  load  with  minimal  transient  voltage.    Toshiba’s 
design  can  handle  100%  step  load  without  using  the  batteries  and  maintaining  a  less  than  
5% voltage distortion, making this UPS configuration the right choice for many customers.