200
P9 ASD Installation and Operation Manual
Under-Voltage Trip Detection Time
Program
Protection
Under-Voltage/Ridethrough
This parameter sets the time that the under-voltage condition must exist to
cause an
Under-Voltage Trip
.
Direct Access Number — F628
Parameter Type —
Numerical
Factory Default —
0.03
Changeable During Run —
No
Minimum — 0.01
Maximum — 10.00
Units — Seconds
Regenerative Power Ridethrough Control Level
Program
Protection
Under-Voltage/Ridethrough
This parameter is activated during regeneration. It is used to set the low end of
the DC bus voltage threshold that, once the bus voltage drops below this
setting, activates the setting of
(Ridethrough Mode).
Activation may be the result of a momentary power loss or an excessive load on
the bus voltage.
During a
Ridethrough
, regenerative energy is used to maintain the control
circuitry settings for the duration of the
Ridethrough
; it is not used to drive the
motor.
The motor(s) of the system is/are stopped and then restarted automatically or
may continue seamlessly if so configured.
See
for additional information on this parameter.
Note:
This parameter setting may increase deceleration times.
Direct Access Number — F629
Parameter Type —
Numerical
Factory Default —
(ASD-Dependent)
Changeable During Run —
No
Minimum — 55
Maximum — 100
Units — %
Brake Answer Delay Time
Program
Protection
Special Protection Parameters
This parameter is used in conjunction with the discrete input terminal setting
Brake Answerback Input
(see
for additional information
on this feature).
After activating the discrete input terminal
Braking Request
, the setting of this
parameter starts a count-down timer in which 1) a
Brake Answerback Input
response must be received or 2) the brake must release before the timer expires.
Should this timer setting expire before the
Brake Answerback Input
is
returned or the brake releases, a
Brake Fault
(E-11) is incurred. Otherwise, the
brake releases and normal motor operations resume.
Direct Access Number — F630
Parameter Type —
Numerical
Factory Default —
0.0 (Disabled)
Changeable During Run —
Yes
Minimum — 0.0 (Disabled)
Maximum — 10.0
Units — Seconds
ASD Overload
Program
Protection
Overload
This parameter is used to protect the ASD from an over-current condition. The
standard overload rating of the P9 ASD is 120% operation for 60 seconds.
This setting allows for the overload protection to be switched from the standard
overload detection means (Thermal Detection and Overload) to thermal
detection only.
Settings:
0 — Thermal Det Overload
1 — Thermal Detection Only
The
Thermal Detection Only
selection is used when multiple devices are
installed horizontally as described on
Direct Access Number — F631
Parameter Type —
Selection List
Factory Default —
Thermal Det
Overload
Changeable During Run —
No
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......