P9 ASD Installation and Operation Manual
169
V/I Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the gain of the
V/I
input terminals.
Note:
See note on
for additional information on the
V/I
terminal.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F471
Parameter Type —
Numerical
Factory Default —
129
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RR Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the bias of the
RR
input terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.
Direct Access Number — F472
Parameter Type —
Numerical
Factory Default —
128
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RR Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the gain of the
RR
input terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F473
Parameter Type —
Numerical
Factory Default —
154
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RX Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the bias of the
RX
input terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.
Direct Access Number — F474
Parameter Type —
Numerical
Factory Default —
127
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......