P9 ASD Installation and Operation Manual
UP/DOWN Frequency (up) Frequency Step
No Path — Direct Access Only
This parameter sets the frequency increase amount for each activation of the
UP/DOWN Frequency (up)
terminal activation. The rate of the frequency
increase is set at Acceleration Time 1 (
).
See
for additional information on this parameter.
Direct Access Number — F265
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
UP/DOWN Frequency (down) Response Time
No Path — Direct Access Only
This parameter sets the system-response delay to the initial activation of the
discrete input terminal
UP/DOWN Frequency (down)
. This parameter also
sets the activation delay of subsequent terminal activations of the
UP/DOWN
Frequency (down)
terminal during an activate-and-hold.
See
for additional information on this parameter.
Direct Access Number — F266
Parameter Type —
Numerical
Factory Default —
0.1
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 10.0
Units — Seconds
UP/DOWN Frequency (down) Frequency Step
No Path — Direct Access Only
This parameter sets the frequency decrease amount for each activation of the
UP/DOWN Frequency (down)
terminal activation. The rate of the frequency
decrease is set at Deceleration Time 1 (
See
for additional information on this parameter.
Direct Access Number — F267
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.00
Maximum — Maximum Freq. (
Units — Hz
Initial UP/DOWN Frequency
No Path — Direct Access Only
At power up or after a reset, this parameter setting is used to provide a starting
frequency for the
UP/DOWN Frequency
function.
See
for additional information on this parameter.
Direct Access Number — F268
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — Lower-Limit Freq. (
)
Maximum — Upper-Limit Freq. (
Units — Hz
Initial UP/DOWN Frequency Rewriting
No Path — Direct Access Only
At power down, and when enabled, this parameter writes the running frequency
into the
location and, upon a system restart, uses this setting as the startup
frequency.
Disable this parameter and set
to the desired startup frequency if the same
starting frequency is required at each startup.
Note:
This parameter setting may be different at each startup when
enabled.
Settings:
0 — Disabled
1 — Enabled (overwrite
at Power Off or Reset)
Direct Access Number — F269
Parameter Type —
Selection List
Factory Default —
Enabled
Changeable During Run —
Yes
Содержание P9
Страница 1: ...TM P9 ASD Install Op Manual TOSHIBA P9 ASD INSTALLATION OPERATION MANUAL DN 64054 004 February 2013 ...
Страница 2: ......
Страница 3: ...Document Number 64054 004 February 2013 P9 ASD Installation Operation Manual TM ...
Страница 4: ......
Страница 280: ...270 P9 ASD Installation and Operation Manual Figure 38 See Tables 17 and 18 for Actual Dimensions ...
Страница 281: ...P9 ASD Installation and Operation Manual 271 Figure 39 See Tables 17 and 18 for Actual Dimensions ...
Страница 282: ...272 P9 ASD Installation and Operation Manual Figure 40 See Tables 17 and 18 for Actual Dimensions ...
Страница 285: ...P9 ASD Installation and Operation Manual 275 Figure 43 See Table 18 for the associated device Dimensions are in in cm ...
Страница 304: ...294 P9 ASD Installation and Operation Manual W W T3 16 Warranty Card 2 W Phase Over Current 265 ...
Страница 305: ......