162-EN
161-EN
– 81 –
1, 5
3
2, 4
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET TEST
TIMER SET
1
Push and hold the button for more
than 4 seconds. TEST appears on the LCD
display and the unit enters the trial mode.
(TEST is indicated on the LCD display
during the test run.)
TEST
2
Push the
button.
3
Push the
button to switch the
running mode to COOL or HEAT.
NOTE
• Do not run the unit in any mode other than COOL or
HEAT.
• You cannot change the temperature setting during
the test run.
• Errors are detected as usual.
TEST
4
Push the
button to stop running
after
fi
nishing the trial run.
The indication on the LCD display returns
to the status of procedure 1.
5
Push the button to exit the trial mode.
(TEST disappears on the LCD display and
the status changes to normal stopped
mode.).
10
Test run
Before test run
Con
fi
rm that the valve of the refrigerate pipe of the
outdoor unit is OPEN.
• Before turning on the power, con
fi
rm that the
resistance between the terminal block of power
supply and the earth is more than 1M
Ω
using a 500V
megohmmeter.
Do not run the unit if it is less than 1M
Ω
.
CAUTION
• Turn on the power and turn on the case heater of
the compressor.
To save the compressor when it is activated, leave
the power on for more than 12 hours.
Methods of test run
¿
When executing a test run using
a remote controller
Operate the system normally to check the running
condition using the wired remote controller. Follow
the instructions in the supplied owner’s manual when
operating the unit.
If you use a wireless remote controller for operations,
follow the instructions in the installation manual
supplied with the indoor unit.
To execute a test run forcibly under the condition that
the thermostat automatically turns the unit off due to
the indoor temperature, follow the procedure below.
The forcible test run will automatically stop after 60
minutes to prevent continuous forcible running and
return to normal running.
CAUTION
Do not use forcible running except for a test run as it
overloads the unit.
¿
When executing a test run using
the interface P.C. board on the
outdoor unit
You can execute a test run by operating switches
on the interface P.C. board of the header outdoor
unit. “Individual trial”, which tests each indoor unit
separately, and “corrective trial”, which tests all the
indoor units connected, are available.
<Individual test operation>
q
Starting operation
1
Set the running mode to “COOL” or
“HEAT” on the remote controller of the
indoor unit to be tested.
(The unit will run in the current mode
unless you set the mode otherwise.)
7-segment display
[A]
[B]
[U1]
[ ]
2
Set the rotary switches on the interface
P.C. board of the header outdoor unit:
SW01 to [16], SW02 and SW03 to the
address of the indoor unit to be tested.
SW02
SW03
Indoor unit address
1 to 16
1
1 to 16
Set number of SW02
1 to 16
2
17 to 32 Set number of SW02 + 16
1 to 16
3
33 to 48 Set number of SW02 + 32
1 to 16
4
49 to 64 Set number of SW02 + 48
7-segment display
[A]
[B]
[ ]
i
Address display of the
corresponding indoor unit
[ ]
3
Push and hold SW04 for more than 10
seconds.
7-segment display
[A]
[B]
[ ]
i
Address display of the
corresponding indoor unit
[ ]
i
[FF] is displayed for 5
seconds.
NOTE
• The running mode follows the mode setting on the
remote controller of the target indoor unit.
• You cannot change the temperature setting during
the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after
turning the power on or stopping running.
q
Finishing operation
1
Set the rotary switches on the interface
P.C. board of the header unit back: SW01
to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
1117101201-3 EN.indd 81
1117101201-3 EN.indd 81
8/8/2559 BE 3:49 PM
8/8/2559 BE 3:49 PM