Outdoor Unit (
14, 16,
18, 20, 22HP)
Model: MMY-MAP
14A6
∗
, MAP16A6
∗
,
MAP
1806
∗
, MAP2006
∗
, MAP2206
∗
1.When compressor No.1 (front left) is faulty
:
Change the connection of wiring between Comp-IPDU and Fan-IPDU as shown in the below.
2.When compressor No.2 (front right) is faulty
:
Change the connection of wiring between Comp-IPDU and Fan-IPDU as shown in the below.
CN22
CN23
CN21
CN23
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU1
・
Change to CN22 of Comp-IPDU2 from CN21 of Comp-IPDU1
・
Change to CN23 of Comp-IPDU2 from CN23 of Comp-IPDU1
(Tighten two wirings together with screw terminal)
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
・
Change to CN22 of Comp-IPDU1 from CN21 of Comp-IPDU2
・
Change to CN23 of Comp-IPDU1 from CN23 of Comp-IPDU2
(Tighten two wirings together with screw terminal)
CN22
CN23
CN21
CN23
(
4
)
Turn on the power supply to all the units connected to the system.
This is the end of compressor backup operation setting.
−
2
4
2
−
Содержание MMY-MAP0806HT7(J)P
Страница 305: ...For HT8 J P HT7 J P HT8 J P ME HT7P ME T8 J P E HT8P A model 1 There is no part for T8 J P E model 1 304 ...
Страница 306: ...For HT8 J P E HT8 J P TR model 305 ...
Страница 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Страница 312: ... 311 For HT8 J P HT7 J P HT8 J P ME HT7P ME T8 J P E HT8P A HT8P C model 1 There is no part for T8 J P E model 1 ...
Страница 313: ... 312 For HT8 J P E HT8 J P TR model ...
Страница 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Страница 319: ... 318 For HT8 J P HT7 J P HT8 J P ME HT7P ME T8 J P E HT8P A HT8P C model 1 There is no part for T8 J P E model 1 ...
Страница 320: ... 319 For HT8 J P E HT8 J P TR model ...
Страница 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Страница 350: ......