7-7-8. Fan Operation Check in Outdoor Unit
This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board
in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function
to check the operation or abnormal sound in the fan system. And, use this function while the system is stopped.
NOTE)
Do not use this function during operation of the compressor. It may damage the compressor.
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/4].
(2) When [F. d] is displayed in 7-segment display [A], keep pressing the switch SW04 for 2 seconds or more.
(3) When [ 63 ] is displayed in 7-segment display [B], the fan starts operation. (Max. mode operation)
(4) After that, by changing the setup number of the switches SW02 and SW03, 7-segment display [B] and the fan
mode are changed.
(Mode output pattern of the fan is as follows.)
[Clear]
This function is cleared by one of the following operations.
(1) When SW01 setting number was changed to other number.
(2) Press-switch SW05 was pressed for 2 seconds or more.
SW02 SW03
7-segment display [B]
Fan mode
1
4
[ 63 ]
63
2
[ 62 ]
62
3
[ 61 ]
61
4
[ 60 ]
60
5
[ 59 ]
59
6
[ 58 ]
58
7
[ 57 ]
57
8
[ 56 ]
56
9
[ 55 ]
55
10
[ 54 ]
54
11
[ 53 ]
53
12
[ 52 ]
52
13
[ 51 ]
51
14
[ 50 ]
50
15
[ 49 ]
49
16
[ 48 ]
48
1
5
[ 47 ]
47
2
[ 46 ]
46
3
[ 45 ]
45
4
[ 44 ]
44
5
[ 43 ]
43
6
[ 42 ]
42
7
[ 41 ]
41
8
[ 40 ]
40
9
[ 39 ]
39
10
[ 38 ]
38
11
[ 37 ]
37
12
[ 36 ]
36
13
[ 35 ]
35
14
[ 34 ]
34
15
[ 33 ]
33
16
[ 32 ]
32
SW02 SW03
7-segment display [B]
Fan mode
1
6
[ 31 ]
31
2
[ 30 ]
30
3
[ 29 ]
29
4
[ 28 ]
28
5
[ 27 ]
27
6
[ 26 ]
26
7
[ 25 ]
25
8
[ 24 ]
24
9
[ 23 ]
23
10
[ 22 ]
22
11
[ 21 ]
21
12
[ 20 ]
20
13
[ 19 ]
19
14
[ 18 ]
18
15
[ 17 ]
17
16
[ 16 ]
16
1
7
[ 15 ]
15
2
[ 14 ]
14
3
[ 13 ]
13
4
[ 12 ]
12
5
[ 11 ]
11
6
[ 10 ]
10
7
[ 9 ]
9
8
[ 8 ]
8
9
[ 7 ]
7
10
[ 6 ]
6
11
[ 5 ]
5
12
[ 4 ]
4
13
[ 3 ]
3
14
[ 2 ]
2
15
[ 1 ]
1
16
[ 0 ]
0
Two fans move synchronously in two fan model (MMY-MAP1806* to MAP2206*).
−
1
4
9
−
Содержание MMY-MAP0806HT7(J)P
Страница 305: ...For HT8 J P HT7 J P HT8 J P ME HT7P ME T8 J P E HT8P A model 1 There is no part for T8 J P E model 1 304 ...
Страница 306: ...For HT8 J P E HT8 J P TR model 305 ...
Страница 307: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 306 ...
Страница 312: ... 311 For HT8 J P HT7 J P HT8 J P ME HT7P ME T8 J P E HT8P A HT8P C model 1 There is no part for T8 J P E model 1 ...
Страница 313: ... 312 For HT8 J P E HT8 J P TR model ...
Страница 314: ... 313 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Страница 319: ... 318 For HT8 J P HT7 J P HT8 J P ME HT7P ME T8 J P E HT8P A HT8P C model 1 There is no part for T8 J P E model 1 ...
Страница 320: ... 319 For HT8 J P E HT8 J P TR model ...
Страница 321: ... 320 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model ...
Страница 350: ......