70-EN
69-EN
– 35 –
Setting when connecting
indoor units to FS (Flow
Selector) unit
¿
Cautions to connection of indoor
unit
• When connecting the indoor units to a single port
type FS unit and a branch of the multi port type FS
unit, it is necessary to set up the CODE No..
Be sure to set up the CODE No. after setup of
address.
• When connecting the indoor units to a single port
type FS unit and a branch of the multi port type FS
unit, it is possible to connect with multiple groups
and connect individually.
Single port type FS unit
Piping
Control wiring
between indoor
unit and FS unit
(Within 15 m)
Remote controller
Group control
Indoor unit
Indoor unit
Piping
Multi port type FS unit (* 1 )
Remote controller
Group control
Indoor unit
Remote controller
Group control
Single port type FS unit
Piping
Incorrect
Control wiring
between indoor
unit and FS unit
Single port type FS unit
Piping
¿
How to set up CODE No. [ 0E ]
It is necessary to set up in case of the group control.
2
4
1
3
.
5
1
Push and hold the , , and buttons
at the same time for more than 4 seconds.
•
is displayed in the UNIT No. window.
• In this time, the fans of all the indoor units in
the group control start the fan operation.
2
Using the set temperature buttons
/
, select the CODE No. “
”.
3
Change SET DATA to “
” by the timer
buttons / .
4
Push button.
5
Push button. Then the setup
fi
nished.
¿
How to set up CODE No. [ FE ]
In cases other than connecting with one indoor unit
or one group in one branching, it is necessary to set
up.
• As for both single port type and multi port type, set
up CODE No. “FE” in one branching within the range
of 1~64.
This CODE No. should not be duplicate in one
system.
¿
How to set up CODE No. [ FD ]
In cases other than connecting with one indoor unit
or one group in one branching, it is necessary to set
up.
0 : Heating prioritized (Factory default)
1 : Cooling prioritized
q
In case of FE/FD without setting
Single port type FS unit
Piping
Control wiring
between indoor
unit and FS unit
(Within 15 m)
Remote controller
Group control
Indoor unit
Indoor unit
Piping
Multi port type FS unit (* 1 )
Remote controller
Group control
q
In case of FE/FD with setting
Single port type FS unit
Single port type FS unit
Piping
Piping
Control wiring
between indoor
unit and FS unit
(Within 15 m)
Control wiring
between indoor
unit and FS unit
(Within 15 m)
Remote controller
Remote
controller
Group control
Group control
Group control
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Piping
Piping
Multi port type FS unit (* 1 )
Multi port type FS unit (* 1 )
Remote
controller
Remote
controller
Group control
Group control
Group control
* 1 : The setting method of Single port type FS unit
(L ong piping model) is same as the one branch
of M ulti port type FS unit.
¿
How to set up CODE No. [ 1 4 ]
1 : Header unit
It is necessary to set up group address in case of
the group control.
0 : Individual
2 : Follower unit
AMP Air Conditioning
www.ampair.co.uk | [email protected]