Push the button.
• The address of one of the indoor units
connected to the selected refrigerant line is
indicated on the LCD display and the fan and
louvers of the unit are activated.
At
fi
rst, the current indoor unit address is
displayed in SET DATA.
(No system address is indicated.)
4
8
5, 7
6
ON / OFF
TEMP.
TIME
SET
CL
FILTER
RESET TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C.
No.
Press to
fi
nish
setting.
Finish
4
Push the TIME / buttons repeatedly
to change the value of the indoor unit
address in SET DATA.
Change the value in SET DATA to that of a
new address.
5
Push the button to con
fi
rm the new
address on SET DATA.
6
Push the
button (left side of the
button) repeatedly to select another
address to change. Each time you push
the button, the indoor unit numbers in
a refrigerant line are indicated one after
another. Only the fan and louvers of the
selected indoor unit are activated.
Repeat steps
4
to
6
to change the indoor unit
addresses so as to make each of them unique.
7
Push the button.
(All the segments on the LCD display light up.)
8
Push the button to
fi
nish the procedure.
Resetting the address
(Resetting to the factory
default (address undecided))
Method 1
Clearing each address separately using a wired
remote controller.
Set the system address, indoor unit address and group
address to “0099” using a wired remote controller.
(For the setting procedure, refer to the address setting
procedures using the wired remote controller on the
previous pages.
)
Method 2
Clearing all the indoor unit addresses on a refrigerate
line at once from the outdoor unit.
1
Turn off the refrigerant line to reset to the
factory default and set the header outdoor
unit of the line as below.
1) Disconnect the relay connectors between the
[U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already
been disconnected.)
2) Turn on DIP switch 2 of SW30 on the
interface P.C. board of the header outdoor
unit if the switch is OFF.
(Leave it as it is if it has already been set to
ON.)
U3 U4
U1 U2
U5 U6
U1 U2
A
B
U3 U4
U1 U2
U5 U6
U1 U2
A
B
U3 U4
U1 U2
U5 U6
U1 U2
A
B
U3 U4
U1 U2
U5 U6
U1 U2
A
B
U3 U4
U1 U2
U1
U3
U2
U4
U5 U6
U1 U2
A
B
Central control
controller
Header
unit
Header
unit
Header
unit
Follower unit
Follower unit
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Indoor units to have their addresses initialized
2
Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
addresses. About one minute after turning on the power, con
fi
rm that the 7-segment display
on the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the
header outdoor unit of the refrigerant line as follows.
SW01
SW02
SW03
SW04
Clearable addresses
2
1
2
Con
fi
rm that the 7-segment display indicates
“A.d.buS” and turn SW04 ON for more than
fi
ve
seconds.
System/indoor unit/group address
2
2
2
Con
fi
rm that the 7-segment display indicates
“A.d.nEt” and turn SW04 ON for more than
fi
ve
seconds.
Central control address
3
Con
fi
rm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
4
After a time “U.1.L08” appears on the 7-segment display if the address clearing has been
completed successfully.
If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other
refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be
cleared.
5
Set the addresses again after
fi
nishing the clearance.