20-EN
19-EN
–
0
1
–
Installation space
Leave space necessary for running, installation and servicing.
Air intake
Air intake
Air discharge
Air intake
Air intake
10mm or more
Installation/servicing
surface
Square hole
for handling
500mm or more
(Rear side)
500mm or more
(Front side)
10mm or more
Outdoor unit top view
20mm or more
20mm or more
NOTE
• If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor
unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
q
Combination of outdoor units (* : FT8P-UK , FT8JPUK )
Model name
Unit 1
Unit 2
Unit 3
MMY-MAP0806*
MMY-MAP0806*
-
-
MMY-MAP1006*
MMY-MAP1006*
-
-
MMY-MAP1206*
MMY-MAP1206*
-
-
MMY-MAP1406*
MMY-MAP1406*
-
-
MMY-MAP1606*
MMY-MAP1606*
-
-
MMY-MAP1806*
MMY-MAP1806*
-
-
MMY-MAP2006*
MMY-MAP2006*
-
-
MMY-AP2216*
MMY-MAP1206*
MMY-MAP1006*
-
MMY-AP2416*
MMY-MAP1406*
MMY-MAP1006*
-
MMY-AP2616*
MMY-MAP1406*
MMY-MAP1206*
-
MMY-AP2816*
MMY-MAP1406*
MMY-MAP1406*
-
MMY-AP3016*
MMY-MAP1606*
MMY-MAP1406*
-
MMY-AP3216*
MMY-MAP1806*
MMY-MAP1406*
-
MMY-AP3416*
MMY-MAP1806*
MMY-MAP1606*
-
MMY-AP3616*
MMY-MAP1806*
MMY-MAP1806*
-
MMY-AP3816*
MMY-MAP2006*
MMY-MAP1806*
-
MMY-AP4016*
MMY-MAP2006*
MMY-MAP2006*
-
MMY-AP4216*
MMY-MAP1406*
MMY-MAP1406*
MMY-MAP1406*
AMP Air Conditioning
www.ampair.co.uk | [email protected]