AIR CONDITIONER (MULTI TYPE)

Installation Manual

Outdoor Unit

Model name:

MMY-MAP0806FT8P-UK
MMY-MAP1006FT8P-UK
MMY-MAP1206FT8P-UK
MMY-MAP1406FT8P-UK
MMY-MAP1606FT8P-UK
MMY-MAP1806FT8P-UK
MMY-MAP2006FT8P-UK

MMY-MAP0806FT8JPUK
MMY-MAP1006FT8JPUK
MMY-MAP1206FT8JPUK
MMY-MAP1406FT8JPUK
MMY-MAP1606FT8JPUK
MMY-MAP1806FT8JPUK
MMY-MAP2006FT8JPUK

For commercial use

English

1117701501

AMP Air Conditioning

www.ampair.co.uk | [email protected]

Содержание MMY-MAP0806FT8JPUK

Страница 1: ...P1206FT8P UK MMY MAP1406FT8P UK MMY MAP1606FT8P UK MMY MAP1806FT8P UK MMY MAP2006FT8P UK MMY MAP0806FT8JPUK MMY MAP1006FT8JPUK MMY MAP1206FT8JPUK MMY MAP1406FT8JPUK MMY MAP1606FT8JPUK MMY MAP1806FT8JPUK MMY MAP2006FT8JPUK For commercial use English 1117701501 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Страница 2: ...ndividual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a...

Страница 3: ...n the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing WARNING Moving parts Do not operate unit with grille rem...

Страница 4: ...utdoor units to the OFF position Otherwise electric shock may result 1 Precautions for safety Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of electric shocks if the circuit breaker is set to ON by mistake Only a qualified installer 1 or qualified service person 1 is allowed to undertake work ...

Страница 5: ... be produced This appliance is intended to be used by expert or trained users in shops in light industry or for commercial use by lay persons Selection of installation location If you install the unit in a small room take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks Consult the dealer from whom you purchased the air conditioner when you im...

Страница 6: ...es insulated shoes and other clothing to provide protection from electric shock Otherwise you may receive an electric shock Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws Use of wiring which does not meet the specifications may give rise to electric shocks electrical leakage smoking and or a fire Check that the product is ...

Страница 7: ... installation work tell the user where the circuit breaker is located If the user does not know where the circuit breaker is he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner If you have discovered that the fan grille is damaged do not approach the outdoor unit but set the circuit breaker to the OFF position and contact a qualified service pers...

Страница 8: ... refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please care so that water or dust does not enter To Disconnect the Appliance from Main Powe...

Страница 9: ...or unit for installation Attached pipe Ø22 2 both forward and downward 1 1 Discharge side gas pipe Ø19 1 Ø22 2 pipe fitting Flare the connector on the outdoor unit for installation Attached pipe Ø12 7 for draw out forward 1 Liquid pipe Flare the connector on the outdoor unit for installation Attached pipe Ø12 7 for draw out downward 1 Part name Q ty Shape Usage MAP080 MAP100 MAP120 MAP140 MAP160 M...

Страница 10: ...rating oil has been also changed Therefore pay attention so that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation To prevent mixing of refrigerant or refrigerating oil the size of the charge port of the main unit or connecting section of the installation tool differs to that of an air conditioner fo...

Страница 11: ...does not exceed 800mm q Combination of outdoor units FT8P UK FT8JPUK Model name Unit 1 Unit 2 Unit 3 MMY MAP0806 MMY MAP0806 MMY MAP1006 MMY MAP1006 MMY MAP1206 MMY MAP1206 MMY MAP1406 MMY MAP1406 MMY MAP1606 MMY MAP1606 MMY MAP1806 MMY MAP1806 MMY MAP2006 MMY MAP2006 MMY AP2216 MMY MAP1206 MMY MAP1006 MMY AP2416 MMY MAP1406 MMY MAP1006 MMY AP2616 MMY MAP1406 MMY MAP1206 MMY AP2816 MMY MAP1406 MMY...

Страница 12: ...chinery for loading unloading in transportation insert the fork of the forklift into the rectangular holes for handling as shown below When lifting up the unit insert a rope able to bear the unit s weight into the rectangular holes for handling and tie the unit from 4 sides Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused to the outer s...

Страница 13: ...ill not be an obstacle for the air intake and the air discharge Snowfall hood for air discharge locally procured Snowfall hood for air intake 4 faces locally procured Stand locally procured 1 To install multiple outdoor units arrange them with 20mm or more spaces in between Fix each outdoor unit with M12 anchor bolts at 4 positions 20mm projection is appropriate for an anchor bolt 20 20mm or more ...

Страница 14: ...tly into the header unit When attaching a Y shaped branch unit for the outdoor unit connection piping kit attach it level with the ground Be sure not to exceed 15 degrees Regarding a T shape branch joints for the liquid side there is no restriction for its angle At a level position A B Horizontal line Horizontal line A arrow view B arrow view Within 15 degrees Within 15 degrees Do not connect a br...

Страница 15: ...ng cycle due to oxidized scale may occur Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant Be sure to use two spanners to loosen or tighten the flare nut If a single spanner is used the required level of tightening cannot be obtained Tighten the flare nut with the specified torque If it is hard to loosen or tighten ...

Страница 16: ...ht difference between the indoor units When the height difference between the indoor units is 15m or less Up to 135 of the capacity code Equivalent to HP of the outdoor unit When the height difference between the indoor units is over 15m Up to 105 of the capacity code Extruding margin of copper pipe with flare machining B Unit mm Copper pipe outer dia When using R410A tool When using conventional ...

Страница 17: ...s 2 Equivalent to HP Equivalent to capacity MMY MAP0806 8 22 4 18 MMY MAP1006 10 28 22 MMY MAP1206 12 33 5 27 MMY MAP1406 14 40 31 MMY MAP1606 16 45 36 MMY MAP1806 18 50 4 40 MMY MAP2006 20 56 41 MMY AP2216 22 61 5 49 MMY AP2416 24 68 54 MMY AP2616 26 73 5 58 MMY AP2816 28 80 63 MMY AP3016 30 85 64 MMY AP3216 32 90 4 64 MMY AP3416 34 95 4 64 MMY AP3616 36 100 8 64 MMY AP3816 38 106 4 64 MMY AP4016...

Страница 18: ...pes Ø9 5 First branch 10 Single port type Flow selector unit Indoor unit 7 Y shaped branching joint Cooling only Cooling only 3 Main piping Discharge side gas pipe Suction side gas pipe Indoor unit 6 6 6 4 2 4 2 7 6 6 6 7 10 Multi port type Flow selector unit 4 4 7 4 4 6 10 Single port type Flow selector unit Long piping model 6 10 4 4 2 7 6 AMP Air Conditioning www ampair co uk sales ampair co uk...

Страница 19: ...s possible only within one FS unit 8 The group connection of the multiple indoor units is possible up to 8 units if one remote controller is used and it is possible up to 7 units if two remote controllers are used The group connection of the multiple indoor units is possible only within one branch or one FS unit Selection of pipe size No Title Use part Selection of pipe size Remarks 1 Outdoor unit...

Страница 20: ... to the outdoor unit and those to indoor units at a right angle as shown in figure 1 on 6 Installation of the outdoor unit Do not connect them as in figure 2 on 6 Installation of the outdoor unit L1 LA La Lb Lc a b c k l f g h L3 L5 L6 L7 L8 d e m n o o i j LO m n L4 c b a Height difference between outdoor units H3 Outdoor unit A Header unit B Follower unit C Follower unit Outdoor unit connecting ...

Страница 21: ...rigerant piping Item Allowable value Pipes Pipe length Total extension of pipe liquid pipe real length Less than 34 HP or less 300 m LA La Lb Lc L1 L2 L3 a b c d e f g h i j k l m n o p q r s t u v 34 HP or more 1000 m 7 Farthest piping length L 1 2 Equivalent length 200 m LA Lc L1 L3 L4 L5 L6 L7 L8 o Real length 180 m Max equivalent length of Main piping H2 3 m Equivalent length 100 m L1 Real len...

Страница 22: ... hours though the time differs depending on the pipe length Check that all the valves at the suction gas side discharge gas side liquid side and balance pipe side are fully closed If the pressure does not reach 100 7kPa or less even after vacuuming for over 2 hours continue vacuuming for 1 hour or more If the pressure does not reach 100 7kPa after 3 hours of vacuuming stop vacuuming and check for ...

Страница 23: ...frigerant slightly by operating the valve of the canister to charge liquid refrigerant The liquid refrigerant may be charged suddenly therefore be sure to charge refrigerant gradually Adding refrigerant After finishing vacuuming exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant Calculation of additional refrigerant charge amount Refrigerant charge am...

Страница 24: ...EU Regulation No 517 2014 on certain fluorinated greenhouse gases and any relevant local legislation 6 Periodical inspections for refrigerant leaks may be required depending on European or local legislation 7 Contact dealers installers etc for any questions Full opening of the valve Open the valves of the outdoor unit fully MAP080 MAP100 MAP120 MAP140 MAP160 MAP180 MAP200 Balance pipe Packed valve...

Страница 25: ...t bridge the power between outdoor units through the equipped terminal blocks L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N Incorrect Power supply for outdoor units Heat insulation for pipe Apply heat insulation of pipe separately at the liquid gas and balance sides Be sure to use thermal insulator resistant up to 120 C or higher for pipes at the gas side Finishing after connecting pipes After pipin...

Страница 26: ...tely RBC CBK15FE Power wiring selection Select the power supply cabling of each outdoor unit from the following specifications Cable 5 core in conformance with design H07 RN F or 60245 IEC 66 To decide nominal cross sectional area of conductor refer to following table of Maximum Overcurrent Protection Amps MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection Amps Model name Power Supply MC...

Страница 27: ...der unit Follower unit Follower unit Follower unit Indoor unit Outdoor unit Remote controller Super modular multi system Table 3 Table 1 Table 2 Table 3 Table 3 Table 1 Remote controller Remote controller Multi port type FS unit and Table 1 Control wiring between indoor and outdoor units L1 L2 L3 Central control wiring L4 Wiring 2 core non polarity Type Shield wire Size Length 1 25 mm2 Up to 1000 ...

Страница 28: ...2 L3 N 10mm or more Attached clamp filter Fixed on attached binding band only MAP160 to MAP200 type Earth line Power supply wire Screw size and tightening torque Screw size Tightening torque N m Power supply terminal M6 2 5 to 3 0 Earth screw M8 5 5 to 6 6 Communication wire connection Get the communication wire through the cutout on the side of the electrical control box and connect it to the com...

Страница 29: ...ure 1 Central control of 2 or more refrigerant lines go to Address setting procedure 2 Example When controlling a single refrigerant line centrally When controlling 2 or more refrigerant lines centrally Address setting procedure To procedure 1 To procedure 2 System wiring diagram Outdoor Outdoor Central remote controller Central remote controller Indoor Indoor Indoor Indoor Remote controller Remot...

Страница 30: ...ne s header indoor unit is set separately In that case the CODE No L03 Indoor header unit overlap is indicated as running starts Change the group address to make one unit the header unit using wired remote controller Example Controlling 2 or more refrigerant lines as a group System wiring diagram Outdoor Outdoor Indoor Indoor Indoor Indoor Remote controller Group control Address setting procedure ...

Страница 31: ...dication U 1 U 1 flash starts flashing on the display When the flashing stops and U 1 U 1 light remains lit on the display the setting is complete 7 Repeat steps 4 to 6 for other refrigerant lines 8 After completing address setting of all systems turn off DIP switch 2 of SW30 on the interface P C boards of all the header outdoor units connected to the same central control except the unit that has ...

Страница 32: ...tion Never connect relay connectors between the U1 U2 and U3 U4 terminals before completing address setting of all the refrigerant lines Otherwise the addresses cannot be set correctly Manual address setting using the remote controller Procedure when setting indoor units addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started manual setting...

Страница 33: ...l devices For the setting of the central control address refer to the installation manuals of the central control devices Confirming the indoor unit addresses and the position of an indoor unit using the remote controller Confirming the numbers and positions of indoor units To see the indoor unit address of an indoor unit which you know the position of q When the unit is individual the indoor unit...

Страница 34: ...ct a system address 3 Push the button to confirm the system address selection The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its fan and louvers are activated 4 Push the button left side of the button Each time you push the button the indoor unit numbers of the selected refrigerant line are indicated one after another Only the fan and l...

Страница 35: ...lay connectors between the U1 U2 and U3 U4 terminals Leave them as they are if they have already been disconnected 2 Turn on DIP switch 2 of SW30 on the interface P C board of the header outdoor unit if the switch is OFF Leave it as it is if it has already been set to ON U3 U4 U1 U2 U5 U6 U1 U2 A B U3 U4 U1 U2 U5 U6 U1 U2 A B U3 U4 U1 U2 U5 U6 U1 U2 A B U3 U4 U1 U2 U5 U6 U1 U2 A B U3 U4 U1 U2 U1 U...

Страница 36: ...p CODE No FE In cases other than connecting with one indoor unit or one group in one branching it is necessary to set up As for both single port type and multi port type set up CODE No FE in one branching within the range of 1 64 This CODE No should not be duplicate in one system How to set up CODE No FD In cases other than connecting with one indoor unit or one group in one branching it is necess...

Страница 37: ...it Within 15 m Remote controller Indoor unit Indoor unit Multi port type FS unit 1 Remote controller 0E 1 1 0 0 14 1 FE 0E 1 1 0 0 14 1 Group control Piping Group control In case of connecting four indoor units Single port type FS unit Piping Control wiring between indoor unit and FS unit Within 15 m Remote controller Indoor unit Indoor unit Multi port type FS unit Remote controller Piping Incorre...

Страница 38: ...o becomes the header unit Every pushing button left side of the button the indoor unit No in the group control is displayed successively CODENo UNIT No R C No SETTING SETTING DATA SET Select an indoor unit of which setting is to be changed In this time the position of the indoor unit of which setup is to be changed can be confirmed because the fan and louver of the selected indoor unit work 3 Use ...

Страница 39: ...ff due to the indoor temperature follow the procedure below The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to normal running CAUTION Do not use forcible running except for a test run as it overloads the unit When executing a test run using the interface P C board on the outdoor unit You can execute a test run by operating switches o...

Страница 40: ...mperature setting during the test run Errors are detected as usual The unit does not perform test run for 3 minutes after turning the power on or stopping running 7 segment display A C H F B C H F q Stop operation 1 Set the rotary switches on the interface P C board of the header unit back SW01 to 1 SW02 to 1 and SW03 to 1 7 segment display A U1 B SW04 SW01 SW02 SW03 D600 D601 D602 D603 D604 SW05 ...

Страница 41: ...01 TE1 sensor 02 TE2 sensor TE1 sensor error TE2 sensor error F07 01 TL1 sensor TL1 sensor error F08 TO sensor error Check code Check code name Indication on 7 segment display on the outdoor unit Auxiliary code F12 01 TS1 sensor 02 TS2 sensor TS1 or TS2 sensor error F13 01 Compressor 1 02 Compressor 2 TH Heat sink sensor error F15 Outdoor temp sensor miswiring TE1 TL1 F16 Outdoor pressure sensor m...

Страница 42: ...essor 1 error 02 Compressor 2 error 03 Compressor 1 and 2 error 08 Fan 1 error 09 Compressor 1 Fan 1 error 0A Compressor 2 Fan 1 error 0B Compressor 1 and 2 Fan 1 error 13Machine card and logbook Machine card After test run fill the items on the machine card and paste the card on an accessible place on the product securely before delivery to the customer Describe the following items on the machine...

Страница 43: ...mall room Medium room Large room Mechanical ventilation device Gas leak detector NOTE 3 The minimum indoor floor area compared with the amount of refrigerant is roughly as follows When the ceiling is 2 7m high 0 5 10 10 20 30 15 20 25 30 35 40 m2 Total amount of refrigerant kg Range below the density limit of 0 3 kg m3 countermeasures not needed Range above the density limit of 0 3 kg m3 counterme...

Страница 44: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1117701501 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Отзывы: