– 7 –
3
System control of Hot Water Module
System able to be combined
The High temperature Hot water module (H-HWM) is connectable to SHRM-e.
In case of connecting at least one Hot water module in SHRM-e system, all of Flow Selector unit type should be Single port type Flow Selector unit (long piping model) or Multi port type Flow Selector unit.
Model name of usable Flow Selector unit: RBM-Y1124FE, RBM-Y1804FE, RBM-Y2804FE, RBM-Y1801F6PE, RBM-Y1801F4PE
The Fresh Air intake type and Air to Air Heat Exchanger with DX Coil cannot be connected with the same refrigerant system.
M-HWM: Mid temperature Hot water module
H-HWM: High temperature Hot water module
HWM: Mid temperature Hot water module and High temperature Hot water module
No.
Item
SHRM-e
1
Indoor connection
capacity(*1)
Total
Standard indoor unit + M-HWM + H-HWM
90 - 200% (*2) (*3)
Standard indoor unit + M-HWM
90 - 135% (*2) (*3)
Allowed
capacity
Standard indoor unit
50 - 120% (*2)
M-HWM
0 - 67.5% (*2) (*3)
H-HWM
0 - 100% (*2) (*3)
M-HWM + H-HWM
0 - 100% (*2) (*3)
2
Maximum indoor unit
quantity
Total
Standard indoor unit + M-HWM + H-HWM
32
Standard indoor unit + M-HWM
32
Allowed
number
Standard indoor unit
2 - 32
M-HWM
0 - 14
H-HWM
0 - 12
M-HWM + H-HWM
0 - 14
3
Height difference
Height difference between outdoor
and indoor units
H1
(*4)
(Including HWM)
H2
>
3 m
Upper outdoor units
50 m
Lower outdoor units
30 m
H2
≤
3 m
Upper outdoor units
70 m
Lower outdoor units
30 m
Height difference between indoor
units
(Including HWM)
H2, H4, H5
(*4)
Indoor - Indoor
H2
Upper outdoor units
40 m
Lower outdoor units
15 m (*6)
HWM - HWM
H4
Upper outdoor units
40 m
Lower outdoor units
15 m (*6)
Indoor - HWM
H5
Upper outdoor units
40 m
Lower outdoor units
15 m (*6)
Height between outdoor units
H3
5 m
Height difference between indoor units in group control by one Flow Selector unit
H6
0.5 m
13-EN
14-EN