– 71 –
Heat exchanger
assembly
No. Part to be replaced
Work procedure
Remarks
7
TC1
TC2 (TWO)
TA (TWI)
TCJ
TF (TCJ2)
2way valve
2way valve
coil drection
coil drection
TC1
TC2 (TWO)
TA (TWI)
TCJ
TF (TCJ2)
For TC2 (TWO) and TC1
Insertion drection :
→
For TA(TWI), TCJ and TF (TCJ2)
Insertion drection :
←
For TC2 (TWO) and TC1
Insertion drection :
→
For TA(TWI), TCJ and TF (TCJ2)
Insertion drection :
←
2way valve
coil drection
Heat exchanger assembly fixing plate
056 type only
200mm
or more
When removing these two screws,
use a screwdriver as shown on the right
Heat exchanger assembly fixing plate
056 type only
200mm
or more
When removing these two screws,
use a screwdriver as shown on the right.
Heat exchanger assembly edge
Heat exchanger assembly edge
Enboss
Enboss
1. Detachment
1) Close the water supply source valve and the valve of
water pipe connected to the unit, carry out the
refrigerant recovery and then remove the refrigerant
and water pipes.
2) Carry out the detachment of item
4
(Electrical control
box) and item
6
(pipe cover plate).
3) Remove the screws for the heat exchanger assembly
fixing plate as shown below.(4x10, 7pcs.)
For the unit for 056 type:4x10, 8pcs.
4) Remove the heat exchanger assembly from the unit as
shown below.
5) Remove sensors, 2way valve coil and flow switch
attached the heat exchanger assembly.
6) Carry out installation by following the detachment
procedure in reverse.
CAUTION
• Be careful in the insertion direction of attaching the
sensor, as shown below.
• Be careful to attach the flow switch, as shown
item
5
(flow switch).
2. Attachment
1) Carry out installation by following the detachment
procedure in reverse.
NOTE:
• To attach the heat exchanger assembly on the proper
position, replace the heat exchanger assembly edge on
the enboss, as shown below.