– 49 –
Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
• Check connection of TC1
sensor connector and
wiring.
• Check resistance
characteristics of TC1
sensor.
• Check for defect in indoor
P.C. board.
Indoor
unit
—
Indoor TC1
sensor error
Stop of
corresponding unit
Sensor resistance is infinity
or zero (open / short circuit).
F03
—
• Check connection of TD1
sensor connector.
• Check resistance
characteristics of TD1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
I/F
—
TD1 sensor
error
All stop
Sensor resistance is infinity
or zero (open / short circuit).
F04
F04
• Check connection of TD2
sensor connector.
• Check resistance
characteristics of TD2
sensor.
• Check for defect in outdoor
P.C. board (I/F).
I/F
—
TD2 sensor
error
All stop
Sensor resistance is infinity
or zero (open / short circuit).
F05
F05
• Check connection of TE1/
TE2 sensor connectors.
• Check resistance
characteristics of TE1/TE2
sensors.
• Check for defect in outdoor
P.C. board (I/F).
I/F
01:
TE1 sensor
error
02:
TE2 sensor
error
TE1/TE2
sensor error
All stop
Sensor resistance is infinity
or zero (open / short circuit).
F06
F06
• Check connection of TL
sensor connector.
• Check resistance
characteristics of TL
sensor.
• Check for defect in outdoor
P.C. board (I/F).
I/F
TL sensor error
All stop
Sensor resistance is infinity
or zero (open / short circuit).
F07
F07
—
• Check connection of TO
sensor connector.
• Check resistance
characteristics of TO
sensor.
• Check for defect in outdoor
P.C. board (I/F).
I/F
TO sensor error All stop
Sensor resistance is infinity
or zero (open / short circuit).
F08
F08
—
• Check connection of TA
sensor connector and
wiring.
• Check resistance
characteristics of TA
sensor.
• Check for defect in indoor
P.C. board.
Indoor unit
Indoor TA
sensor error
Stop of
corresponding unit
Sensor resistance is infinity
or zero (open / short circuit).
F10
—
—
• Check connection of TF
sensor connector and
wiring.
• Check resistance
characteristics of TF
sensor.
• Check for defect in indoor
P.C. board.
Indoor unit
Indoor TF
sensor error
Stop of
corresponding unit
Sensor resistance is infinity
or zero (open / short circuit).
F11
—
—
• Check connection of TS1
sensor connector.
• Check resistance
characteristics of TS1
sensor.
• Check for defect in outdoor
P.C. board (I/F).
I/F
TS1 sensor
error
All stop
Sensor resistance is infinity
or zero (open / short circuit).
F12
F12
—
• Defect in IGBT built-in
temperature sensor
→
Replace A3-IPDU P.C.
board.
IPDU
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
TH sensor error All stop
Sensor resistance is infinity
or zero (open / short circuit).
F13
F13
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
Indoor unit (including Hot Water Module)