– 5 –

• Tighten the 

fl

 are nut with a torque wrench in the speci

fi

 ed 

manner. Excessive tighten of the 

fl

 are nut may cause a crack in 

the 

fl

 are nut after a long period, which may result in refrigerant 

leakage.

• After the installation work, con

fi

 rm that refrigerant gas does 

not leak. If refrigerant gas leaks into the room and 

fl

 ows near 

fi

 re source, such as a cooking range, noxious gas may be 

generated.

• When the air conditioner has been installed or relocated, 

follow the instructions in the Installation Manual and purge 

the air completely so that no gases other than the refrigerant 

will be mixed in the refrigerating cycle. Failure to purge the air 

completely may cause the air conditioner to malfunction.

• Nitrogen gas must be used for the airtight test.

• The charge hose must be connected in such a way that it is not 

slack.

Electrical wiring

• Only a quali

fi

 ed installer(*1) or quali

fi

 ed service person(*1) is 

allowed to carry out the electrical work of the air conditioner. 

Under no circumstances must this work be done by an 

unquali

fi

 ed individual since failure to carry out the work 

properly may result in electric shocks and/or electrical leaks.

• To connect the electrical wires, repair the electrical parts 

or undertake other electrical jobs, wear gloves to provide 

protection for electricians and from heat, insulating shoes and 

clothing to provide protection from electric shocks.

Failure to wear this protective gear may result in electric 

shocks.

• Use wiring that meets the speci

fi

 cations in the Installation 

Manual and the stipulations in the local regulations and laws. 

Use of wiring which does not meet the speci

fi

 cations may give 

rise to electric shocks, electrical leakage, smoking and/or a 

fi

 re.

• Connect earth wire. (Grounding work)

Incomplete grounding causes an electric shock.

• Do not connect earth wires to gas pipes, water pipes, and 

lightning conductor or telephone earth wires.

• After completing the repair or relocation work, check that the 

earth wires are connected properly.

• Install a circuit breaker that meets the speci

fi

 cations in the 

installation manual and the stipulations in the local regulations 

and laws.

• Install the circuit breaker where it can be easily accessed by the 

agent.

• When installing the circuit breaker outdoors, install one which is 

designed to be used outdoors.

• Under no circumstances the power wire must not be extended. 

Connection trouble in the places where the wire is extended 

may give rise to smoking and/or a 

fi

 re.

• Electrical wiring work shall be conducted according to law and 

regulation in the community and installation manual.

Failure to do so may result in electrocution or short circuit.

Test run

• Before operating the air conditioner after having completed the 

work, check that the electrical control box cover of the indoor 

unit and service panel of the outdoor unit are closed, and set 

the circuit breaker to the ON position. You may receive an 

electric shock if the power is turned on without 

fi

 rst conducting 

these checks.

• If there is any kind of trouble (such as an error display 

has appeared, smell of burning, abnormal sounds, the air 

conditioner fails to cool or heat or water is leaking) has occurred 

in the air conditioner, do not touch the air conditioner yourself 

but set the circuit breaker to the OFF position, and contact a 

quali

fi

 ed service person. Take steps to ensure that the power 

will not be turned on (by marking “out of service” near the circuit 

breaker, for instance) until quali

fi

 ed service person arrives. 

Continuing to use the air conditioner in the trouble status may 

cause mechanical problems to escalate or result in electric 

shocks or other trouble.

• After the work has 

fi

 nished, use an insulation tester set 

(500V Megger) to check the resistance is 1M

Ω

 or more between 

the charge section and the non-charge metal section 

(Earth section). If the resistance value is low, a disaster such 

as a leak or electric shock is caused at user’s side.

9-EN

10-EN

Содержание MMU-UP0091HP-E

Страница 1: ...llation Manual Indoor Unit Model name 4 way Cassette Type For commercial use English MMU UP0091HP E MMU UP0121HP E MMU UP0151HP E MMU UP0181HP E MMU UP0241HP E MMU UP0271HP E MMU UP0301HP E MMU UP0361HP E MMU UP0481HP E MMU UP0561HP E ...

Страница 2: ... Accessory parts 7 3 Selection of installation place 7 4 Installation 9 5 Drain piping 11 6 Refrigerant piping 12 7 Electrical connection 13 8 Applicable controls 17 9 Test run 19 10 Maintenance 20 11 Troubleshooting 22 12 Specifications 27 Information If U series models TU2C Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indo...

Страница 3: ...he has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation repair relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipu...

Страница 4: ...lified installer or service person is allowed to do installation work Inappropriate installation may result in water leakage electric shock or fire Do not use any refrigerant different from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body...

Страница 5: ... flammable gas leaks are possible If the gas leak and accumulate around the unit it may ignite and cause a fire To transport the air conditioner wear shoes with additional protective toe caps To transport the air conditioner do not take hold of the bands around the packing carton You may injure yourself if the bands should break Install the indoor unit at least 2 5 m above the floor level since ot...

Страница 6: ...tor or telephone earth wires After completing the repair or relocation work check that the earth wires are connected properly Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws Install the circuit breaker where it can be easily accessed by the agent When installing the circuit breaker outdoors install one which ...

Страница 7: ...left open and the compressor still operating will cause air or other gas to be sucked in raising the pressure inside the refrigeration cycle to an abnormally high level and possibly resulting in rupture injury or other trouble CAUTION New refrigerant air conditioner installation This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410...

Страница 8: ... servicing space can be ensured for safety maintenance and check Place where drained water will not cause any problem Avoid installing in the following places Place exposed to air with high salt content seaside area or place exposed to large quantities of sulfide gas KRW spring Should the unit be used in these places special protective measures are needed A restaurant kitchen where a lot of oil is...

Страница 9: ...ly Provide an inspection opening at the outside air intake box side Check port Check port REQUIREMENT When using the air conditioner with 2 way 3 way discharge system a strong wind blows directly if the ceiling height is lower than the standard Therefore change the setting switch according to height of the ceiling When using the high ceiling 1 or 3 with 4 way discharge system the draft is apt to b...

Страница 10: ...eiling already exists lay the drain pipe refrigerant pipe indoor unit outdoor unit connection wires and remote controller wires to their connection locations before hanging the indoor unit Procure hanging bolts and nuts for installing the indoor unit these are not supplied Using the installation pattern accessory The installation pattern is provided inside the packaging cap For existing ceiling Us...

Страница 11: ...according to Installation Manual attached with it after piping wiring work has completed Check that installation of indoor unit and ceiling opening part is correct and then install it REQUIREMENT Joint the connecting sections of ceiling panel ceiling surface ceiling panel and indoor unit closely Any gap between them will cause air leakage and the generate condensation or water leakage Remove the a...

Страница 12: ...xible hose Soft socket Hard socket Socket for VP25 Locally procured Indoor unit Drain pipe connecting port Transparent Flexible hose Accessory Socket for VP25 vinyl chloride pipe Locally procured VP25 vinyl chloride pipe Locally procured Indoor unit 5 mm or less 10 mm hose band tightening margin Heat insulator 10 to 12 mm Connecting drain pipe Connect a hard socket locally procured to the hard soc...

Страница 13: ... height difference They vary depending on the outdoor unit For details refer to the Installation Manual attached to the outdoor unit Pipe size Connecting refrigerant piping Flaring 1 Cut the pipe with a pipe cutter Remove burrs completely Remaining burrs may cause gas leakage 2 Insert a flare nut into the pipe and flare the pipe Use the flare nut provided with the unit or the one used for the R410...

Страница 14: ...plete connection or fixation may cause a fire or other trouble Connect earth wire grounding work Incomplete grounding cause an electric shock Do not connect earth wires to gas pipes water pipes lightning conductor or telephone earth wires Appliance shall be installed in accordance with national wiring regulations Capacity shortage of power circuit or incomplete installation may cause an electric s...

Страница 15: ... UP This letter indicates U series model Other than U series MM AP Wired remote controller RBC ASCU This letter indicates U series model Other than U series Wireless remote controller kit receiver unit RBC AXU This letter indicates U series model Other than U series U series outdoor unit SMMS u MMY MUP Other than U series outdoor unit SMMS i SMMS e etc MMY MHP In the case of combining with outdoor...

Страница 16: ... Ln In case of wired type only Up to 500 m In case of wireless type included Up to 400 m Total wire length of remote controller inter unit wiring L1 L2 Ln Up to 200 m L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller Remote controller wiring 7KH UHPRWH FRQWUROOHU ZLUH RPPXQLFDWLRQ OLQH DQG 9 ZLUHV FDQQRW EH SDUDOOHO WR FRQWDFW HDFK RWK...

Страница 17: ...unit wire Remote controller terminal block Cord clamp Earth wire Power supply wire Uv U1 Uv U2 A B Remote controller wiring As the remote controller wire has non polarity there is no problem if connections to indoor unit terminal blocks A and B are reversed Wiring diagram A B A B Terminal block for remote controller wiring of indoor unit Remote controller wire Field supply Terminal block Remote co...

Страница 18: ...akes up to 10 minutes usually about 5 minutes When the power is turned on after automatic address setup It takes up to 10 minutes usually about 3 minutes for the outdoor unit to start operating after the power has been turned on Before the air conditioner was shipped from the factory all units are set to STANDARD factory default If necessary change the indoor unit settings The settings are changed...

Страница 19: ...FF 0003 OFF ON MCU IC501 SW501 2 SW501 1 Change of lighting time of filter sign According to the installation condition the lighting time of the filter sign Notification of filter cleaning can be changed Follow the basic operation procedure 1 2 3 4 5 6 For the CODE No in Procedure 4 specify 01 For the SET DATA in Procedure 5 select the SET DATA of filter sign lighting time from the following table...

Страница 20: ...or this control By using insulation tester 500VMΩ check that resistance of 1MΩ or more exists between the terminal block L to N and the earth grounding If resistance of less than 1MΩ is detected do not run the unit HIRUH WXUQLQJ RQ WKH FLUFXLW EUHDNHU FDUU RXW WKH following procedure Before starting a test run be sure to set addresses following the installation manual supplied with the outdoor uni...

Страница 21: ...o 5 7 Upon completion of the test run push ON OFF button to stop operation Overview of test run operations using the wireless remote controller Cooling test run ON OFF 17 C 18 C 17 C 18 C 17 C 18 C 17 C test run ON OFF Heating test run ON OFF 30 C 29 C 30 C 29 C 30 C 29 C 30 C test run ON OFF 10Maintenance Cleaning of panel and air filter Preparation 1 Turn off the air conditioner by the remote co...

Страница 22: ... s expense Failure to clean the indoor and outdoor units regularly will result in poor performance freezing water leakage and even compressor failure Inspection before maintenance Following inspection must be carried out by a qualified installer or qualified service person Maintenance List d o h t e m n o i t c e p s n I s t r a P Heat exchanger Access from inspection opening and remove the access...

Страница 23: ...mode has been entered If Service check is displayed the mode enters in the troubleshooting history mode 01 Order of troubleshooting history appears in the temperature indicator The OFF timer indicator alternately shows the check code and the indoor Unit No in which the problem occurred 2 Each time the setting button is pushed the recorded troubleshooting history is displayed in sequence The troubl...

Страница 24: ...etected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote controller E10 Commun...

Страница 25: ... sensor trouble I F F24 F24 ALT Pd sensor trouble I F F29 SIM Indoor unit other trouble Indoor unit F30 F30 SIM Occupancy sensor trouble Indoor unit F31 F31 SIM Indoor unit EEPROM trouble I F H01 H01 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor break down Inverter H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side Compressor trouble lock Inverter H03 H03 01 Comp 1 side 02 Comp 2 side ...

Страница 26: ... P01 ALT Indoor fan motor trouble Indoor unit P03 P03 ALT Discharge temp TD1 trouble I F P04 P04 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT High pressure SW system operation Inverter P05 P05 00 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage trouble comp I F ...

Страница 27: ...ble 1 2 1 2 01 Comp 1 02 Comp 2 03 Comp 1 Comp 2 08 Fan1 09 Comp 1 Fan1 0A Comp 2 Fan1 0B Comp 1 Comp 2 Fan1 10 Fan2 11 Comp 1 Fan2 12 Comp 2 Fan2 13 Comp 1 Comp 2 Fan2 18 Fan1 Fan2 19 Comp 1 Fan1 Fan2 1A Comp 2 Fan1 Fan2 1B All Inverter trouble For details about check codes determined with an Interface P C board or an Inverter P C board refer to the Installation Manual of the outdoor unit Trouble...

Страница 28: ...Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMU UP0241HP E MMU UP0271HP E MMU UP0301HP E MMU UP0361HP E MMU UP0481HP E MMU UP0561HP E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of the Ma...

Страница 29: ...conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards for ...

Страница 30: ...3 0003 High ceiling setup CODE NO 5d F NO CHANGE 0000 F STANDARD 0001 F HIGH CEILING 1 0002 F HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 F NO CHANGE F NONE 0000 F 150H 0001 F 2500H 0002 F 500...

Страница 31: ...1115350194 144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand ...

Отзывы: