– 14 –
EN
ID
ID
Power supply
Control wiring, Central controller wiring
2-core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central
controller wiring.
To prevent noise trouble, use 2-core shield wire.
The length of the communication line means the total length of the inter-unit wire length between indoor and
outdoor units added with the central control system wire length.
Power supply
220-240V ~, 50 Hz
Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by the
accumulated total current values of the indoor units.
Power supply wiring
Below 50 m
2.5 mm
2
208-230V ~, 60 Hz
▼
Communication line
TU2C-Link models (U series) can be combined with TCC-Link models (other than U series).
For details of communication type, refer to the following table.
Communication type and model names
Communication
type
TU2C-Link
(U series and future models)
TCC-Link
(Other than U series)
Outdoor unit
MMY-MUP
This letter indicates U series model.
Other than U series
MMY-MHP
MCY-MHP
MMY-MAP
Indoor unit
MM -UP
This letter indicates U series model.
Other than U series
MM -AP
Wired remote
controller
RBC-ASCU
This letter indicates U series model.
Other than U series
Wireless remote
controller kit &
receiver unit
RBC-AXU
This letter indicates U series model.
Other than U series
U series outdoor unit : SMMS-u (MMY-MUP
)
Other than U series outdoor unit : SMMS-i, SMMS-e etc. (MMY-MHP
)
<In the case of combining with outdoor units of Super Modular Multi System u series (SMMS-u)>
Uv
line and
Uc
line
(L2, L3, L4)
(2-core shield wire, non-polarity)
Wire size :
0.5 mm²
0.75 to 1.25 mm²
(Up to 500 m)
(Up to 1000 m)
Uh
line
(L1)
(2-core shield wire, non-polarity)
Wire size :
0.75 to 1.25 mm²
2.0 mm²
(Up to 1000 m)
(Up to 2000 m)
•
U (v, h, c)
line means of control wiring.
Uv
line : Between indoor and outdoor units.
Uh
line : Central control line.
Uc
line : Between outdoor and outdoor units.
•
Uv
line and
Uc
line are independent from another refrigerant line. Total length of
Uv
and
Uc
lines
(L3+L4)
in each refrigerant line is up to 1000 m.
[Uh line]
L1
= Up to 2000 m
[Uv and Uc line]
L2
= Up to 1000 m
(L3+L4)
= Up to 1000 m
Central control device
<U series>
Outdoor unit
(SMMS-u)
<U series>*
Indoor unit
<U series>*
Remote controller
*Even if the indoor unit and the remote controller are “other than U series”, the wiring
specification are the same.