How to cancel louver lock
Set the wind direction to “
0000
” of the louver lock
setup procedure above.
0000
Setting data
•
When the setting is canceled, goes out.
Other operations are the same as those in
“How to set up louver lock (No swing)”.
■
To select horizontal wind
direction
The louver positions at cooling can be changed from
the smudge reducing position to the cold draftless
position.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
•
Specify
[45]
for the Code NO. in Procedure
4
.
•
Select the following data for the SET DATA in
Procedure
5
.
Wind
direction
SET DATA
Wind direction setting
0000
Smudge reducing position
(Air direction to reduce ceiling
contamination) [Factory default]
0002
Cold draft position
(Air direction to control cold air fall)
For wiring procedure and wiring method of the
individual line (Identical refrigerant line) system,
refer to “Electrical connection” in this Manual.
Wiring between indoor units in a group is performed
in the following procedure.
Connect the indoor units by connecting the remote
controller inter-unit wires from the remote controller
terminal blocks (A/B) of the indoor unit connected
with a remote controller to the remote controller
terminal blocks (A/B) of the other indoor unit.
(Non-polarity)
For address setup, refer to the Installation Manual
attached to the outdoor unit.
Remote controller sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote controller sensor
to sense the temperature around the remote controller.
Select items following the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
Specify
[32]
for the CODE No. in Procedure
4
.
Select the following data for the SET DATA in
Procedure
5
.
When
flashes, the remote controller sensor is
defective.
Select the SET DATA [0000] (not used) or replace the
remote controller.
SET DATA
0000
0001
Remote controller
sensor
Not used
(factory default)
Used
9
Test run
Before test run
1)
2) Check the valve of the outdoor unit being opened
fully.
To protect the compressor at activation time, leave
power-ON for 12 hours or more be for operating.
Group control
7KHZLUHGUHPRWHFRQWUROOHURQO\FDQFRQWURODJURXS
control. The wireless remote controller is unavailable
for this control.
By using insulation tester (500VM
Ω
), check that
resistance of 1M
Ω
or more exists between the
terminal block L to N and the earth (grounding).
If resistance of less than 1M
Ω
is detected, do not
run the unit.
%HIRUHWXUQLQJRQWKHFLUFXLWEUHDNHUFDUU\RXWWKH
following procedure.
Before starting a test run, be sure to set addresses
following the installation manual supplied with the
outdoor unit.
◆
Requirements for turning
thermostat OFF
Cooling operation
•
When the outdoor/suction air temperature is lower
than or equal to 19 °C.
•
When the outdoor/suction air temperature is lower
than or equal to 3 °C above the set temperature.
Heating operation
•
When the outdoor/suction air temperature is lower
than or equal to -10 °C
•
When the outdoor/suction air temperature is higher
than or equal to 15 °C.
•
When the outdoor/suction air temperature is higher
than or equal to 3 °C above the set temperature.
■
Execute a test run
•
When a fan operation is to be performed for an
individual indoor unit, turn off the power, short
circuit CN72 on the circuit board, and then turn the
power back on. (Set the operation mode to “fan”
to operate the unit.) When the test run has been
performed using this method, be sure to release the
short circuit of CN72 after the test run is completed.
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the
attached Owner’s Manual to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by
thermostat-OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than
the test run because it applies an excessive load
to the devices.
Wired remote controller
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
1
Push and hold OFF timer button and
[ ] setting button simultaneously for
10 seconds or more. [TEST] is displayed
on the display part and the test run is
permitted.
2
Push ON/OFF button.
3
Push menu button to select the
operation mode. Select [ Cool] or
[
Heat] with [ ] [ ] setting button,
and then push menu button (three times)
again to determine the operation mode.
•
Do not run the air conditioner in a mode other
than [Cool] or [Heat].
•
The temperature setting function does
notwork during test run.
•
The check code is displayed as usual.