– 120 –
F06
F06
01: TE1 sensor
02: TE2 sensor
03: TE3 sensor
ALT
TE1,TE2 or TE3 sensor trouble
I/F
F07
F07
01: TL1 sensor
02: TL2 sensor
03: TL3 sensor
ALT
TL1,TL2 or TL3 sensor trouble
I/F
F08
F08
—
ALT
TO sensor trouble
I/F
F09
F09
01: TG1 sensor
02: TG2 sensor
03: TG3 sensor
ALT
TG1,TG2 or TG3 sensor trouble
I/F
F10
—
—
ALT
Indoor unit TA sensor trouble
Indoor unit
F11
—
—
ALT
TF sensor trouble
Indoor unit
F12
F12
01: TS1 sensor
03: TS3 sensor
04: TS3 sensor disconnect
ALT
TS1 or TS3 sensor trouble
I/F
F13
F13
1 : Compressor 1 side
2 : Compressor 2 side
ALT
TH sensor trouble
Compressor inverter
F15
F15
—
ALT
Outdoor unit temp. sensor miswiring (
ТЕ
, TL)
I/F
F16
F16
—
ALT
Outdoor unit pressure sensor miswiring (Pd, Ps)
I/F
F22
F22
—
ALT
TD3 sensor trouble
I/F
F23
F23
—
ALT
Ps sensor trouble
I/F
F24
F24
—
ALT
Pd sensor trouble
I/F
F29
—
—
SIM
Indoor unit other trouble
Indoor unit
F30
F30
—
SIM
Occupancy sensor trouble
Indoor unit
F31
F31
—
SIM
Indoor unit EEPROM trouble
I/F
H01
H01
1 : Compressor 1 side
2 : Compressor 2 side
Compressor break down
Compressor inverter
H02
H02
1 : Compressor 1 side
2 : Compressor 2 side
Compressor trouble (lock)
Compressor inverter
H03
H03
1 : Compressor 1 side
2 : Compressor 2 side
Current detect circuit system trouble
Compressor inverter
H04
H04
—
Compressor 1 case thermostat operation
I/F
H05
H05
—
TD1 sensor miswiring
I/F
H06
H06
—
Low pressure protective operation
I/F
H07
H07
—
Oil level down detective protection
I/F
H08
H08
01: TK1 sensor trouble
02: TK2 sensor trouble
03: TK3 sensor trouble
04: TK4 sensor trouble
05: TK5 sensor trouble
Oil level detective temp. sensor trouble
I/F
H14
H14
—
Compressor 2 case thermostat operation
I/F
H15
H15
—
TD2 sensor miswiring
I/F
H16
H16
01: TK1 oil circuit system trouble
02: TK2 oil circuit system trouble
03: TK3 oil circuit system trouble
04: TK4 oil circuit system trouble
05: TK5 oil circuit system trouble
Oil level detective circuit trouble
I/F
H17
H17
1 : Compressor 1 side
2 : Compressor 2 side
Compressor trouble (Step out)
I/F
H25
H25
—
TD3 sensor miswiring
I/F
J02
—
—
SIM
Communication trouble between control boards in Flow Selector unit
Indoor unit
Check code
Wireless remote controller
Check code name
Judging device
Wired remote
controller display
Outdoor unit 7-segment display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
239-EN
240-EN
Содержание MMU-UP0091H-E
Страница 129: ... 128 MEMO ...