31-EN
Installation Manual
– 31 –
EN
EN
Change of lighting time of filter
sign
According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
For the CODE No. in Procedure
4
, specify [01].
For the [SET DATA] in Procedure
5
, select the
SET DATA of filter sign lighting time from the
following table.
To secure better effect of heating
When it is difficult to obtain satisfactory heating due
to installation place of the indoor unit or structure of
the room, the detection temperature of heating can
be raised. Also use a circulator, etc. to circulate
heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
For the CODE No. in Procedure
4
, specify [06].
For the SET DATA in Procedure
5
, select the
SET DATA of shift value of detection
temperature to be set up from the table below.
SET DATA
Filter sign lighting time
0000
None
0001
150H (Factory setting)
0002
2500H
0003
5000H
0004
10000H
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C
0003
+3°C (Factory setting)
0004
+4°C
0005
+5°C
0006
+6°C
SET DATA
Detection temp shift value
0000
No shift
0001
+1°C
0002
+2°C (Factory setting)
0003
+3°C
0004
+4°C
0005
+5°C
0006
+6°C
6
Push OFF timer button.
By doing so, the setup is completed.
•
To change other settings of the selected
indoor unit, repeat from Procedure
4
.
7
When all the settings have been
completed, push ON/OFF button to
determine the settings.
“
”
fl
ashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “
” is
fl
ashing.)
•
To change settings of another indoor unit,
repeat from Procedure
1
.