6
• To increase effect of drain, confirm the unit is
installed horizontally or slightly lowering rightward
viewed from the front side.
• Do not install the unit by plugging in the wall.
• The mass including installation plate of the indoor
unit is shown in the following table. Check whether
the wall has sufficient intensity.
Lowering rightward viewed
from the front side
Lowering leftward viewed
from the front side
Horizontal installation
Indoor unit
Side plate fixing screws
Square hole
Hook
Screw cap
Model MMK-
0071H to 0121H
0151H to 0181H
0241H
Mass (kg)
20
22
29
• When installing the side plate, check the status that
hook is inserted in square hole. Push in the side
plate until it is stuck closely to the indoor unit.
Installation of installation plate
• Using the installation pattern, determine the installation position of the indoor unit, and drill the pipe hole matching
with the position indicated in the installation pattern. When passing the refrigerant pipe through wall using metal
mesh, be sure to use insulation sleeve such as polyvinyl chloride pipe.
In case of wooden construction (Wide wall)
(1) Determine vertical position of the installation plate by interval (height) between the indoor unit and the ceiling.
(2) Determine the position so that screw hole of installation plate locates at the center of pillar or stud by adjusting
left/right position without changing height of the installation plate.
(3) Tighten the screws (accessory parts) after bore preholes with a gimlet in the stud to prevent the crack.
In case of reinforced concrete construction
(1) After drilling holes with interval by 150mm at the selected
positions on the concrete wall, strike in grip anchor or
hole-in anchor.
(2) Fix the installation plate to the anchor with bolt or nut.
However, when using hole-in anchor, adjust drilling depth
so that screw head-out is 10mm or less.
REQUIREMENT
• Conduit tube may be buried in the concrete wall. Ask the constructor it.
• Before installation of the indoor unit, be sure to check whether the installation plate has been completely
installed.
In case of rear direction piping
Using the installation pattern, determine the pipe hole position, and drill a pipe hole slightly lowering downward.
Grip anchor
Hole-in anchor
Bolt
Installation plate
Installation
plate
Concrete
wall
Concrete
wall
Nut
screw
dia. Ø8
10mm
or less
ENGLISH.pmd
2004/07/20, 14:48
Page 6