1
Accessory parts and Parts to be procured locally
Accessory parts
Parts to be procured locally
Connecting pipe (Liquid side)
(6.4mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)
MMK-AP0071H to MMK-AP0181H
(9.5mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)
MMK-AP0241H
Connecting pipe (Gas side)
(9.5mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)
MMK-AP0071H to MMK-AP0121H
(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm)
MMK-AP0151H to MMK-AP0181H
(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm)
MMK-AP0241H
Power supply cord
Cable 3-core 2.5mm
2
,
in conformity with Design 60245 IEC57
<Separate sold parts>
Part name
Standard wired
remote controller
Q’ty
1
Shape
Usage
Model
RBC-AMT21E
Refrigerant piping
• Piping material used for the conventional refrigerant
cannot be used.
• Use copper pipe with 0.8 mm or more thickness for
Ø6.4, Ø9.5, Ø12.7.
Use copper pipe with 1.0 mm or more thickness for
Ø15.9.
• Flare nut and flare works are also different from those
of the conventional refrigerant. Take out the flare nut
attached to the indoor unit of the air conditioner, and
use it.
Part name
Installation
Manual
Heat
insulating pipe
Wood screw
M4 × 35L
Installation
plate
Q’ty
1
2
12
1
Shape
This
manual
Usage
(Be sure to hand over to customers)
For heat insulation of pipe
connecting section
For attach the installation plate
Used install indoor unit wall unit
Part name
Installation
pattern
Screw cap
Banding band
Q’ty
1
4
4
Shape
—
Usage
For confirmation of piping hole
and indoor unit position
Cover on fixing screw at side plate
Used to fix attached pipe heat
insulating material