Toshiba MMF-UP0151H-E Скачать руководство пользователя страница 24

– 23 –

F06

F06

01: TE1 sensor
02: TE2 sensor
03: TE3 sensor

ALT

TE1,TE2 or TE3 sensor trouble

I/F

F07

F07

01: TL1 sensor
02: TL2 sensor
03: TL3 sensor

ALT

TL1,TL2 or TL3 sensor trouble

I/F

F08

F08

ALT

TO sensor trouble

I/F

F09

F09

01: TG1 sensor
02: TG2 sensor
03: TG3 sensor

ALT

TG1,TG2 or TG3 sensor trouble

I/F

F10

ALT

Indoor unit TA sensor trouble

Indoor unit

F11

ALT

TF sensor trouble

Indoor unit

F12

F12

01: TS1 sensor
03: TS3 sensor

ALT

TS1 or TS3 sensor trouble

I/F

F13

F13

01: Comp. 1 side          1d: Comp. 1 side
02: Comp. 2 side          2d: Comp. 2 side
03: Comp. 3 side

ALT

TH sensor trouble

Compressor inverter

F15

F15

ALT

Outdoor unit temp. sensor miswiring (

ТЕ

, TL)

I/F

F16

F16

ALT

Outdoor unit pressure sensor miswiring (Pd, Ps)

I/F

F22

F22

ALT

TD3 sensor trouble

I/F

F23

F23

ALT

Ps sensor trouble

I/F

F24

F24

ALT

Pd sensor trouble

I/F

F29

SIM

Indoor unit other trouble

Indoor unit

F30

F30

SIM

Occupancy sensor trouble

Indoor unit

F31

F31

SIM

Indoor unit EEPROM trouble

I/F

H01

H01

01: Comp. 1 side          1 : Comp. 1 side
02: Comp. 2 side          2 : Comp. 2 side
03: Comp. 3 side

Compressor break down

Compressor inverter

H02

H02

01: Comp. 1 side          1 : Comp. 1 side
02: Comp. 2 side          2 : Comp. 2 side
03: Comp. 3 side

Compressor trouble (lock)

Compressor inverter

H03

H03

01: Comp. 1 side          1 : Comp. 1 side
02: Comp. 2 side          2 : Comp. 2 side
03: Comp. 3 side

Current detect circuit system trouble

Compressor inverter

H04

H04

Comp. 1 case thermostat operation

I/F

H05

H05

TD1 sensor miswiring

I/F

H06

H06

Low pressure protective operation

I/F

H07

H07

Oil level down detective protection

I/F

H08

H08

01: TK1 sensor trouble
02: TK2 sensor trouble
03: TK3 sensor trouble
04: TK4 sensor trouble
05: TK5 sensor trouble

Oil level detective temp. sensor trouble

I/F

H14

H14

Comp. 2 case thermostat operation

I/F

H15

H15

TD2 sensor miswiring

I/F

H16

H16

01: TK1 oil circuit system trouble
02: TK2 oil circuit system trouble
03: TK3 oil circuit system trouble
04: TK4 oil circuit system trouble
05: TK5 oil circuit system trouble

Oil level detective circuit trouble

I/F

H25

H25

TD3 sensor miswiring

I/F

Check code

Wireless remote controller

Check code name

Judging device

Wired remote 

controller display

Outdoor unit 7-segment display

Sensor block display of receiving unit

Auxiliary code

Operation

Timer

Ready

Flash

45-EN

46-EN

Содержание MMF-UP0151H-E

Страница 1: ...TIONER MULTI TYPE Installation Manual R410A Indoor Unit Floor Standing Type MMF UP0151H E MMF UP0181H E MMF UP0241H E MMF UP0271H E MMF UP0361H E MMF UP0481H E MMF UP0561H E Model name For commercial use English ...

Страница 2: ...Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indoor units will be changed Pay attentions to their communication specifications when carrying out the installation maintenance or repair For its details refer to the Electrical connection in this Manual Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of insta...

Страница 3: ... work involved in installation repair relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or indi...

Страница 4: ...fferent from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the O...

Страница 5: ... Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakag...

Страница 6: ...t first conducting these checks If there is any kind of trouble such as check code display has appeared smell of burning abnormal sounds the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner do not touch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take steps to ensure that the power ...

Страница 7: ...oil enter the refrigerating cycle during installation work To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the R410A refrigerant For connecting pipes use new and clean piping designed fo...

Страница 8: ...ron or other metal dust is present If iron or other metal dust adheres to or collects on the interior of the air conditioner it may spontaneously combust and start a fire Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit t...

Страница 9: ...f possible If carrying in the indoor unit unpacked by necessity use buffering cloth or other material not to damage the unit Carry the package by four or more persons and do not bundle it with plastic band at positions other than specified Be sure to take measures to prevent falling at the wall surface and the floor and fix it surely considering prevention of accident of falling because this unit ...

Страница 10: ...oor unit to the wall surface using the attached screw bolts anchor bolts or etc at two positions Many holes for fixing the indoor unit to wall surface and for fixing the indoor unit itself are provided on the bracket Sliding the bracket right and left sides select a position which can securely fix the indoor unit and then fix it A hole on the wall fixing bracket for the indoor unit is a long hole ...

Страница 11: ...are hole in the rear case and the hole in the remote controller panel Upper Cabinet Screws fastening upper cabinet 2 pieces Cords 2 pieces Intake Grille Foam Cover Remote Controller Panel Pins 4 pieces Screws fastening foam cover 2 pieces Decorative Panel Screws 2 pieces Mounting Bracket of Remote Controller 4 1 Mount the remote controller onto the rear case mounted on the mounting bracket in 3 2 ...

Страница 12: ...wet furniture After opening the knockout hole deburr the edge Touching burrs adhered to opening of the knockout hole may cause an injury Following the Installation Manual perform the drain hose work Inappropriate drain hose work may result in generation of slime in the drain hose and water leakage in the room NOTE The drain pipe and drain hose must be sloping downward at an angle of 1 100 or more ...

Страница 13: ...e hard to remove the drip proof cover and the electrical control box cannot be taken out Drain hose Drain pan Heat insulator Hard polyvinyl chloride pipe Adhesion for hard polyvinyl chloride pipe used To connect drain hose on right or left route it through the knock out for refrigerant piping on UP015 to UP027 model Wiring port both sides Refrigerant pipe connecting port both sides Piping port at ...

Страница 14: ... surface Model MMF Outside diamerer side mm Gas side Liquid side UP015 UP018 12 7 6 4 UP024 to UP056 15 9 9 5 Outside diameter size mm R410A tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 15 9 Outside diameter size mm A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 B A Tightening connection CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tigh...

Страница 15: ...s completes Power supply wire and communication wires specifications Power supply wire and communication wires are locally procured For the power supply specifications follow to the table below If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attac...

Страница 16: ...re models other than U series their system diagrams for the wiring specifications are the same as the system diagram above SMMS u U series In the case of combining with outdoor units other than Super Modular Multi System u series SMMS u The length of the communication line L1 L2 L3 means the total length of the inter unit wire length between indoor and outdoor units added with the central control ...

Страница 17: ...t type Outdoor unit U series U series U series U series Indoor unit U series U series U series U series Remote controller Remote sensor U series U series U series U series Communication type TU2C Link TCC Link Max number of connectable units 16 8 L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller Remote controller wiring For number of m...

Страница 18: ...e terminal block Be sure to mount cover of the electrical control box and the drip proof cover 1 3 4 2 Drip proof cover UP015 to UP027 only Electrical control box cover Electrical control box R S U1 U2 A B N L R L S N Uv U1 Uv U2 A B Positioning of hole for wiring Knock out hole UP015 to UP027 UP036 to UP056 Wiring hole Knock out hole Wiring hole Knock out hole Earth screw Power supply wiring Cord...

Страница 19: ...ton is pushed indoor unit numbers in the group control change cyclically Select the indoor unit to change settings for The fan of the selected indoor unit runs The indoor unit can be confirmed for which to change settings 3 Push OFF timer button to confirm the selected indoor unit 4 Push the menu button to make Code No flash Change Code No with setting button 5 Push the menu button to make Set dat...

Страница 20: ...ure 1 By using insulation tester 500 VMΩ check that resistance of 1 MΩ or more exists between the terminal block L to N and the earth grounding If resistance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully To protect the compressor at activation time leave power ON for 12 hours or more for operating Before starting a test run be sure to se...

Страница 21: ...fter confirming a signal receiving sound beep immediately set the temperature to 29 C with the temp setup buttons Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 17 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 30 C with the temp setup buttons 10 Maintenance Daily m...

Страница 22: ...earance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ceiling panel louvres Indoor Dust dirt scratches ...

Страница 23: ...unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote controller E10 Communication trouble be...

Страница 24: ... 03 Comp 3 side Compressor break down Compressor inverter H02 H02 01 Comp 1 side 1 Comp 1 side 02 Comp 2 side 2 Comp 2 side 03 Comp 3 side Compressor trouble lock Compressor inverter H03 H03 01 Comp 1 side 1 Comp 1 side 02 Comp 2 side 2 Comp 2 side 03 Comp 3 side Current detect circuit system trouble Compressor inverter H04 H04 Comp 1 case thermostat operation I F H05 H05 TD1 sensor miswiring I F ...

Страница 25: ...2 Comp 2 side 2E Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage trouble comp I F P07 P07 01 Comp 1 side 1C Comp 1 side 02 Comp 2 side 2C Comp 2 side 03 Comp 3 side 04 Heat sink ALT Heat sink overheat trouble Heat sink dew condensation trouble Compressor inverter I F P10 P10 Detecte...

Страница 26: ... 2 Fan 12 Comp 2 Fan2 0B Comp 1 Comp 2 Fan 13 Comp 1 Comp 2 Fan2 0C Comp 3 Fan 18 Fan1 Fan2 0D Comp 1 Comp 3 Fan 19 Comp 1 Fan1 Fan2 0E Comp 2 Comp 3 Fan 1A Comp 2 Fan1 Fan2 0F All 1B All Inverter trouble Inverter trouble Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxil...

Страница 27: ... Fuji shi Shizuoka ken 416 8521 JAPAN TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMF UP0151H E MMF UP0181H E MMF UP0241H E MMF UP0271H E MMF UP0361H E MMF UP0481H E MMF UP0561H E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi Syst...

Страница 28: ...ooms or install mechanical ventilation combined with a gas leak detection device The concentration is as given below Refrigerant Concentration Limit shall be in accordance with local regulations NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The ...

Страница 29: ... 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively...

Страница 30: ...EB99841501 ...

Отзывы: