Toshiba MMF-UP0151H-E Скачать руководство пользователя страница 15

– 14 –

7

Electrical connection

WARNING

Use the specified wires for wiring connection to the terminals. Securely fix them to prevent external forces 
applied to the terminals from affecting the terminals.

Incomplete connection or fixation may cause a fire or other trouble.

Connect earth wire. (grounding work)

Incomplete earthing cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning conductor or telephone earth wires.

Appliance shall be installed in accordance with national wiring regulations.

Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.

CAUTION

The wire size and wire length of the communication line differs depending on the outdoor unit series to be 
connected.

• If incorrect / incomplete wiring is carried out, it will cause an electrical fire or smoke.
• Install an earth leakage breaker that is not tripped by shock waves.

If an earth leakage breaker is not installed, an electric shock may be caused.

• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and inner insulator of power and control wires when peeling them.
• Use the power supply wire and control wires of specified thickness, type, and protective devices required.
• Do not connect 208 V to 240 V power to the terminal blocks (Uv (U1)), (Uv (U2)), (A), (B) for control wiring. 

(Otherwise, the system will fail.)

• Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.

The coating may melt resulting in an accident.

REQUIREMENT

• For power supply wiring, strictly conform to the Local Regulation in each country.
• For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.
• After connecting wires to the terminal blocks, provide a trap and fix wires with the cord clamp.
• Run the refrigerant piping line and communication line in the same line.
• Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.

Power supply wire and communication wires specifications

Power supply wire and communication wires are locally procured.
For the power supply specifications, follow to the table below. If capacity is little, it is dangerous because overheat 
or burnout may be caused.
For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the Installation 
Manual attached to the outdoor unit.

Indoor unit power supply

• For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor 

unit.

• Arrange the power supply, circuit breaker, and main switch of the indoor unit connected to the same outdoor unit 

so that they are commonly used.

• Power supply wire specification: Cable 3-core 2.5 mm², 

in conformity with Design 60245 IEC 57

.

Power supply

Control wiring, Central controller wiring

• 2-core with non-polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central 

controller wiring.

• To prevent noise trouble, use 2-core shield wire.

Communication line

TU2C-Link models (U series) can be combined with TCC-Link models (other than U series). 
For details of communication type, refer to the following table.

Communication type and model names

U series outdoor unit: SMMS-u (MMY-MUP

)

Other than U series outdoor unit: SMMS-i, SMMS-e etc. (MMY-MAP

)

Power supply

220 V - 240 V, 50 Hz

208 V - 230 V, 60 Hz

Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by 

the accumulated total current values of the indoor units.

Power supply wiring

Below 50 m

3 × 2.5 mm

2

 (power supply and earth)

Communication

type

TU2C-Link

(U series and future models)

TCC-Link

(Other than U series)

Outdoor unit

MMY-MUP

Other than U series

MMY-MAP

MCY-MHP

Indoor unit

MM -UP

Other than U series

MM -AP

Wired remote

controller

RBC-A

U

Other than U series

Wireless remote

controller kit &

receiver unit

RBC-AXU

Other than U series

Remote sensor

TCB-TC

U

Other than U series

This letter indicates U series model.

This letter indicates U series model.

This letter indicates U series model.

This letter indicates U series model.

This letter indicates U series model.

27-EN

28-EN

Содержание MMF-UP0151H-E

Страница 1: ...TIONER MULTI TYPE Installation Manual R410A Indoor Unit Floor Standing Type MMF UP0151H E MMF UP0181H E MMF UP0241H E MMF UP0271H E MMF UP0361H E MMF UP0481H E MMF UP0561H E Model name For commercial use English ...

Страница 2: ...Link are combined with models other than U series TCC Link the wiring specifications and maximum number of connectable indoor units will be changed Pay attentions to their communication specifications when carrying out the installation maintenance or repair For its details refer to the Electrical connection in this Manual Contents 1 Precautions for safety 3 2 Accessory parts 7 3 Selection of insta...

Страница 3: ... work involved in installation repair relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or indi...

Страница 4: ...fferent from the one specified for complement or replacement Otherwise abnormally high pressure may be generated in the refrigeration cycle which may result in a failure or explosion of the product or an injury to your body Before opening the intake grille of the indoor unit or service panel of the outdoor unit set the circuit breaker to the OFF position Failure to set the circuit breaker to the O...

Страница 5: ... Installation Install the air conditioner securely in a location where the base can sustain the weight adequately If the strength is not enough the unit may fall down resulting in injury Follow the instructions in the Installation Manual to install the air conditioner Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise vibration water leakag...

Страница 6: ...t first conducting these checks If there is any kind of trouble such as check code display has appeared smell of burning abnormal sounds the air conditioner fails to cool or heat or water is leaking has occurred in the air conditioner do not touch the air conditioner yourself but set the circuit breaker to the OFF position and contact a qualified service person Take steps to ensure that the power ...

Страница 7: ...oil enter the refrigerating cycle during installation work To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the R410A refrigerant For connecting pipes use new and clean piping designed fo...

Страница 8: ...ron or other metal dust is present If iron or other metal dust adheres to or collects on the interior of the air conditioner it may spontaneously combust and start a fire Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will be disrupted a disruption of the air flow may cause the air conditioner s performance to deteriorate or the unit t...

Страница 9: ...f possible If carrying in the indoor unit unpacked by necessity use buffering cloth or other material not to damage the unit Carry the package by four or more persons and do not bundle it with plastic band at positions other than specified Be sure to take measures to prevent falling at the wall surface and the floor and fix it surely considering prevention of accident of falling because this unit ...

Страница 10: ...oor unit to the wall surface using the attached screw bolts anchor bolts or etc at two positions Many holes for fixing the indoor unit to wall surface and for fixing the indoor unit itself are provided on the bracket Sliding the bracket right and left sides select a position which can securely fix the indoor unit and then fix it A hole on the wall fixing bracket for the indoor unit is a long hole ...

Страница 11: ...are hole in the rear case and the hole in the remote controller panel Upper Cabinet Screws fastening upper cabinet 2 pieces Cords 2 pieces Intake Grille Foam Cover Remote Controller Panel Pins 4 pieces Screws fastening foam cover 2 pieces Decorative Panel Screws 2 pieces Mounting Bracket of Remote Controller 4 1 Mount the remote controller onto the rear case mounted on the mounting bracket in 3 2 ...

Страница 12: ...wet furniture After opening the knockout hole deburr the edge Touching burrs adhered to opening of the knockout hole may cause an injury Following the Installation Manual perform the drain hose work Inappropriate drain hose work may result in generation of slime in the drain hose and water leakage in the room NOTE The drain pipe and drain hose must be sloping downward at an angle of 1 100 or more ...

Страница 13: ...e hard to remove the drip proof cover and the electrical control box cannot be taken out Drain hose Drain pan Heat insulator Hard polyvinyl chloride pipe Adhesion for hard polyvinyl chloride pipe used To connect drain hose on right or left route it through the knock out for refrigerant piping on UP015 to UP027 model Wiring port both sides Refrigerant pipe connecting port both sides Piping port at ...

Страница 14: ... surface Model MMF Outside diamerer side mm Gas side Liquid side UP015 UP018 12 7 6 4 UP024 to UP056 15 9 9 5 Outside diameter size mm R410A tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 15 9 Outside diameter size mm A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 B A Tightening connection CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tigh...

Страница 15: ...s completes Power supply wire and communication wires specifications Power supply wire and communication wires are locally procured For the power supply specifications follow to the table below If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attac...

Страница 16: ...re models other than U series their system diagrams for the wiring specifications are the same as the system diagram above SMMS u U series In the case of combining with outdoor units other than Super Modular Multi System u series SMMS u The length of the communication line L1 L2 L3 means the total length of the inter unit wire length between indoor and outdoor units added with the central control ...

Страница 17: ...t type Outdoor unit U series U series U series U series Indoor unit U series U series U series U series Remote controller Remote sensor U series U series U series U series Communication type TU2C Link TCC Link Max number of connectable units 16 8 L1 L L2 Ln Indoor unit Remote controller inter unit wiring Indoor unit Indoor unit Indoor unit Remote controller Remote controller wiring For number of m...

Страница 18: ...e terminal block Be sure to mount cover of the electrical control box and the drip proof cover 1 3 4 2 Drip proof cover UP015 to UP027 only Electrical control box cover Electrical control box R S U1 U2 A B N L R L S N Uv U1 Uv U2 A B Positioning of hole for wiring Knock out hole UP015 to UP027 UP036 to UP056 Wiring hole Knock out hole Wiring hole Knock out hole Earth screw Power supply wiring Cord...

Страница 19: ...ton is pushed indoor unit numbers in the group control change cyclically Select the indoor unit to change settings for The fan of the selected indoor unit runs The indoor unit can be confirmed for which to change settings 3 Push OFF timer button to confirm the selected indoor unit 4 Push the menu button to make Code No flash Change Code No with setting button 5 Push the menu button to make Set dat...

Страница 20: ...ure 1 By using insulation tester 500 VMΩ check that resistance of 1 MΩ or more exists between the terminal block L to N and the earth grounding If resistance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully To protect the compressor at activation time leave power ON for 12 hours or more for operating Before starting a test run be sure to se...

Страница 21: ...fter confirming a signal receiving sound beep immediately set the temperature to 29 C with the temp setup buttons Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 17 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 30 C with the temp setup buttons 10 Maintenance Daily m...

Страница 22: ...earance Replace the fan when vibration or balance is terrible Brush or wash the fan when it is contaminated Air intake discharge grilles Indoor outdoor Dust dirt scratches Fix or replace them when they are deformed or damaged Drain pan Indoor Dust dirt clogging drain contamination Clean the drain pan and check the downward slope for smooth drainage Ceiling panel louvres Indoor Dust dirt scratches ...

Страница 23: ...unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received Decrease of No of indoor units I F E07 Communication circuit trouble between indoor outdoor unit Detected at outdoor unit side I F E08 E08 Duplicated indoor unit addresses Duplicated indoor unit addresses Indoor unit I F E09 Duplicated master remote controllers Remote controller E10 Communication trouble be...

Страница 24: ... 03 Comp 3 side Compressor break down Compressor inverter H02 H02 01 Comp 1 side 1 Comp 1 side 02 Comp 2 side 2 Comp 2 side 03 Comp 3 side Compressor trouble lock Compressor inverter H03 H03 01 Comp 1 side 1 Comp 1 side 02 Comp 2 side 2 Comp 2 side 03 Comp 3 side Current detect circuit system trouble Compressor inverter H04 H04 Comp 1 case thermostat operation I F H05 H05 TD1 sensor miswiring I F ...

Страница 25: ...2 Comp 2 side 2E Comp 2 side 03 Comp 3 side ALT Phase missing detection Power failure detection Inverter DC voltage trouble comp Inverter DC voltage trouble comp Inverter DC voltage trouble comp I F P07 P07 01 Comp 1 side 1C Comp 1 side 02 Comp 2 side 2C Comp 2 side 03 Comp 3 side 04 Heat sink ALT Heat sink overheat trouble Heat sink dew condensation trouble Compressor inverter I F P10 P10 Detecte...

Страница 26: ... 2 Fan 12 Comp 2 Fan2 0B Comp 1 Comp 2 Fan 13 Comp 1 Comp 2 Fan2 0C Comp 3 Fan 18 Fan1 Fan2 0D Comp 1 Comp 3 Fan 19 Comp 1 Fan1 Fan2 0E Comp 2 Comp 3 Fan 1A Comp 2 Fan1 Fan2 0F All 1B All Inverter trouble Inverter trouble Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display Sensor block display of receiving unit Auxil...

Страница 27: ... Fuji shi Shizuoka ken 416 8521 JAPAN TCF holder TOSHIBA CARRIER EUROPE S A S Route de Thil 01120 Montluel FRANCE Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMF UP0151H E MMF UP0181H E MMF UP0241H E MMF UP0271H E MMF UP0361H E MMF UP0481H E MMF UP0561H E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi Syst...

Страница 28: ...ooms or install mechanical ventilation combined with a gas leak detection device The concentration is as given below Refrigerant Concentration Limit shall be in accordance with local regulations NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The ...

Страница 29: ... 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Have you changed detected temp shift value If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively...

Страница 30: ...EB99841501 ...

Отзывы: