Check code
Location
of
detection
Description
System status
Trouble
detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
E08 E08
Duplicated indoor address
Indoor
unit
I/F
Duplicated
indoor address
All stop
More than one indoor unit
are
assigned same address.
• Check indoor addresses.
• Check for any change
made to remote controller
connection (group/
individual) since indoor
address setting.
E09 –
–
Remote
controller
Duplicated
master remote
controller
Stop of
corresponding
unit
In two remote controller
configuration (including
wireless), both controllers are
set up as master. (Header
indoor unit is shut down with
alarm, while follower indoor
units continue operating.)
• Check remote controller
settings.
• Check remote controller
P.C. boards.
E10 –
–
Indoor
unit
UART
communication
trouble
Stop of
corresponding
unit
Communication cannot be
established/maintained upon
turning on of power or during
communication.
• Check for defect in indoor
P.C. board
E12 E12
I/F
Automatic
address starting
trouble
All stop
• Indoor automatic address
setting is started while
automatic address setting
for equipment in other
refrigerant line is in
progress.
• Outdoor automatic
address setting is started
while automatic address
setting for indoor units is in
progress.
• Perform automatic address
setting again after
disconnecting
communication cable to
that refrigerant line.
E15 E15
–
I/F
Indoor unit not
found during
automatic
address setting
All stop
Indoor unit cannot be
detected after indoor
automatic address setting is
started.
• Check connection of
indoor-outdoor
communication line.
• Check for error in indoor
power supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for defect in indoor
P.C. board.
E16 E16
00:
Overloading
01-:
No. of units connected
I/F
Too many
indoor units
connected
All stop
• Combined capacity of
indoor units exceeds 135%
of combined capacity of
outdoor units.
Note:
If this code comes up
after backup setting for
outdoor unit failure is
performed, perform “No
overloading detected”
setting.
<“No overloading detected”
setting method>
Turn on SW09/Bit 2 on I/F
P.C. board of outdoor header
unit.
• More than
64
indoor units
are connected.
• Check capacities of indoor
units connected.
• Check combined HP
capacities of indoor units.
• Check HP capacity
settings of outdoor units.
• Check No. of indoor units
connected.
• Check for defect in outdoor
P.C. board (I/F).
01:
Indoor-outdoor
communication
02:
Outdoor-outdoor
communication
−
64
−
(MCC-1643 and MCC-1610)
Indoor
Application
control kit
communication
trouble
S
top
Displayed when
trouble
is
detected
1. Check connector indoor
unit (CN521(red))
Application control kit
(CN1 (red))
2. Check connection of
indoor-Application control
kit communication line.
3. Check indoor P.C. board.
4. Check Application control
kit P.C. board.
E1
1
–
Communication
error between
Application control
kit and indoor unit
Indoor
unit