21
–
NO.
Item
Specification outline
Remarks
5
1. The fan operates in one of the four speed modes of “HIGH (HH)”, “MED
(H)”, “LOW (L)” and “AUTO” on the basis of a command issued via the
remote controller. (Concealed duct high static pressure type: HH only)
2. In AUTO fan speed mode, the air speed changes according to the
difference between
TA and TS
.
<Cooling>
Fan speed
control
HH > H+ > H >
L+ > L > UL
or LL
TA
(˚C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
–0.5
HH <HH>
H+ <HH>
H <HH>
L+ <H+>
L <H>
L <H>
L <L+>
D
C
B
A
E
F
G
• Control is identical in remote controller thermo and body thermo
operation.
Speed modes shown in < > apply to cooling operation under AUTO air
conditioner operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 3 minutes
each time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
• At the beginning of cooling operation, a higher speed (steeper downward
temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the
fan speed stays the same.
<Heating>
TA
(˚C)
(–0.5) –1.0
(0) Tsh
(+0.5) +1.0
(+1.0) +2.0
(+1.5) +3.0
(+2.0) +4.0
L <L+>
L+ <H>
H <H+>
HH
<HH>
H+
<HH>
E
D
C
B
A
Figures inside ( ) applies to remote controller
thermostat
operation.
Figures outside ( ) applies to body
thermostat
operation.
Speed modes shown in < > apply to heating operation under AUTO air
conditioner operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 1 minute
each time a speed change occurs.
However, a speed change command issued via the remote controller can
override this, and the fan speed changes accordingly.
• At the beginning of heating operation, a higher speed (steeper upward
temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the
fan speed stays the same.
• When TC2
≥
60 °C, the fan speed is raised by one step.
3. If the air conditioner goes
thermostat
OFF during heating operation, the
fan
speed drops down to LL (breeze).
DN code “32”
“0000”: Body
thermostat
“0001”: Remote
controller
thermostat
TC2: Indoor heat
exchanger sensor
temperature
“HEATING
STANDBY
”
displayed
AMP Air Conditioning
www.ampair.co.uk | [email protected]