37
–
8-
5
. Applied control of indoor unit
Control system using Remote location ON/OFF control box (TCB-IFCB-4E2)
Wiring and setting
• In the case of group control, the control system functions as long as it is connected to one of the indoor units
(control P.C. board) in the group. If it is desired to access the operation and error statuses of other units,
relevant signals must be brought to it from those units individually.
Start / stop of unit
Output present while unit in normal operation
Control items
(1)
Start / Stop input signal
(2)
In-operation signa
(3)
Alarm
signal Output
present while alarm (e.g. serial communication error or operation of protective
device for indoor / outdoor unit) being activated
Wiring diagram of control system using
Remote location ON/OFF control box
(TCB-IFCB
-
4E2)
Input
Output
IFCB4E2: No-voltage ON / OFF serial signal
No-voltage contact (in-operation and
alarm
indication)
Contact capacity: Max. AC 240 V, 0.5 A
1
2
3
4
5
6
CN61
T10
(Yellow)
1
2
3
4
1
2
3
4
5
6
CN13
CN06
ON side
Start signal input
Indoor control P.C. board
TCB-IFCB
-
4E2
Start/Stop input
COM (GND)
Remote controller
disabling
/ ending input
In-operation signal output
COM (+12V)
Alarm
signal output
OFF side
Stop signal input
COM
In-operation signal output
Alarm
signal output
Power supply 220-240V