background image

– 22 –

SMMS Slim Duct Type

Installation Manual

EN

SMMS Slim Duct Type

Installation Manual

Check method

On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation 
is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor unit 7-segment display” in the list.
• In case of check from AI-NET central control remote controller: See “AI-NET central control display” in the list.
• In case of check from indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list.

: Lighting,  : Flashing,  : Goes off

AI-NET: Artificial Intelligence

IPDU: Intelligent Power Drive Unit

ALT: Flashing is alternately when there are two flashing LED.

SIM: Simultaneous flashing when there are two flashing LED.

Check code

Wireless remote controller

Check code name

Judging device

Wired remote 

controller display

Outdoor unit 7-segment display

AI-NET central 

control display

Sensor block display of receiving unit

Auxiliary code

Operation

Timer

Ready

Flash

E01

Communication error between indoor unit and remote controller (Detected at 

remote controller side)

Remote controller

E02

Remote controller transmission error

Remote controller

E03

97

Communication error between indoor unit and remote controller (Detected at 

indoor unit side)

Indoor unit

E04

04

Communication circuit error between indoor / outdoor unit (Detected at indoor 

unit side)

Indoor unit

E06

E06

No. of indoor units in which sensor has been 

normally received

04

Decrease of No. of indoor units

I/F

E07

Communication circuit error between indoor / outdoor unit (Detected at 

outdoor unit side)

I/F

E08

E08

Duplicated indoor unit addresses

96

Duplicated indoor unit addresses

Indoor unit • I/F

E09

99

Duplicated master remote controllers

Remote controller

E10

CF

Communication error between indoor unit MC

Indoor unit

E12

E12

01:Indoor / Outdoor units communication
02:Outdoor / Outdoor units communication

42

Automatic address start error

I/F

E15

E15

42

No indoor unit during automatic addressing

I/F

E16

E16

00:Capacity over
01 ~:No. of connected units

89

Capacity over / No. of connected indoor units

I/F

E18

97, 99

Communication error between header and follower units Indoor unit

Indoor unit

E19

E19

00:No header
02:Two or more header units

96

Outdoor header units quantity error

I/F

E20

E20

01:Outdoor unit of other line connected
02:Indoor unit of other line connected

42

Other line connected during automatic address

I/F

E21

E21

02:No header unit
00:Multiple number of header units

42

Error in number of heat storage master units

I/F

E22

E22

42

Reduction in number of heat storage units

I/F

E23

E23

15

Sending error in communication between outdoor units
Error in number of heat storage units (trouble with reception)

I/F

E25

E25

15

Duplicated follower outdoor addresses

I/F

E26

E26

No. of outdoor units which received signal 

normally

15

Decrease of No. of connected outdoor units

I/F

E28

E28

Detected outdoor unit number

d2

Follower outdoor unit error

I/F

E31

E31

Number of IPDU (*1)

CF

IPDU communication error

I/F

43-EN

44-EN

+00EH99879301_01EN.book  Page 22  Tuesday, March 15, 2011  8:42 PM

Содержание MMD-AP0074SPH-E

Страница 1: ...sh Indoor Unit Model name Slim Duct Type MMD AP0074SPH E MMD AP0094SPH E MMD AP0124SPH E MMD AP0154SPH E MMD AP0184SPH E AIR CONDITIONER MULTI TYPE Installation Manual 00EH99879301_01EN book Page 1 Tuesday March 15 2011 8 42 PM ...

Страница 2: ... piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructe...

Страница 3: ...pair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burn...

Страница 4: ...ance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Suction duct length must be longer than 850 mm When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If th...

Страница 5: ...er It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or vibration may result When carrying out the pump down work shut down the compressor before disconnecting the refrigerant pipe Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or oth...

Страница 6: ... trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inv...

Страница 7: ...erm setup of the filter sign Notification of filter cleaning of the remote controller can be changed according to the condition of installation For setup method refer to Filter sign setting in the Applicable controls of this Manual Remove the cover plate and then fix it to the bottom surface Do surely hooking to the main unit Main unit after remover Air filter Main unit Air filter Force Remove the...

Страница 8: ... 103 21 20 40 359 372 422 502 19 21 21 163 Ø 9 2 31 Installation of hanging bolt Consider the piping wiring after the unit is hung to determine the location of the indoor unit installation and orientation After the location of the indoor unit installation has been determined install hanging bolts For the dimensions of the hanging bolt pitches refer to the external view When a ceiling already exist...

Страница 9: ...10 Nut W3 8 or M10 8 m or less 5 Drain Piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site ...

Страница 10: ...e and hose band for connecting the drain hose to the clear drain socket If applying the adhesive socket will be damaged and cause water leakage Align the attached hose band to the end of hose set the tightening position upward and then tighten it Flexible hose Accessory Socket for VP25 vinyl chloride pipe locally procured Drain pipe connecting port Hard socket VP25 vinyl chloride pipe locally proc...

Страница 11: ...ts and seams of the heat insulator upward to avoid water leakage Wrap the attached heat insulator seamlessly from the surface of the indoor unit Flexible hose Hose band Attached heat insulator Heat insulator to be procured locally Hard vinyl chloride pipe 6 Duct Design Arrangement Unit mm Referring to the following dimensions manufacture duct at the local site Under air intake Back air intake 805 ...

Страница 12: ...lete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop Flange locally procured Aluminum tape locally procured Aluminum tape locally procured Under surface Cover a screw Heat insulator with sticking material 100 mm width locally procured Aluminum tape locally procured Air discharge side Indoor unit Air intake side Connect a duct to the inside of...

Страница 13: ...static pressure 20 Pa External static pressure Pa Air Volume m3 h Filter attached AP007 AP009 AP012 AP015 AP018 0 10 20 30 40 50 60 300 400 500 600 700 Standard air volume 540 m3 h Upper limit of external static pressure 50 Pa High 50 Pa Lower limit of externa static pressure 50 Pa Low 50 Pa High 20 Pa Low 35 Pa Low 20 Pa High 10 Pa Low 10 Pa Upper limit of external static pressure 35 Pa Upper lim...

Страница 14: ...0 to 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 Work using double spanner Use the tightening torque levels as listed in the table below Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units...

Страница 15: ...e power supply specifications follow to the table below If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from...

Страница 16: ...Pass the wires through the bushing of wire connection holes of the indoor unit Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing or other purpose The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit Before remove the electrical control box cover remove the cover plate and air filter Remove the cover of the el...

Страница 17: ...ange the indoor unit settings The settings are changed by operating the wired remote controller The settings cannot be changed using only a wireless remote controller simple remote controller or group control remote controller by itself so install a wired remote controller separately as well Basic procedure for changing settings Change the settings while the air conditioner is not working Stop the...

Страница 18: ... 6 Specify 5d to the CODE No in procedure 3 For the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table Change on wired remote controller With a remote controller less system group control Besides the switching method using the wired remote controller as a way to establish the external static pressure switching is also possible by changin...

Страница 19: ... Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C SET DATA 0000 0001 Remotecontroller sensor Not used Factory default Used 10Test Run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L to N and the e...

Страница 20: ...n finished stop the air conditioner from the wireless remote controller and return Dip switch of the receiver section as before A 60 minutes timer clearing function is attached to the receiver section in order to prevent a continuous test operation Small screw Nameplate Notch M4 25 screw 2 pieces Spacer Receiver unit 11Maintenance Daily maintenance Cleaning of air filter If is displayed on the rem...

Страница 21: ... service person Maintenance List Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine the heat exchanger if there is any clogging or damages Fan motor Access from inspection opening and check if any abnormal noise can be heard Fan Access from inspection opening and remove the access panel Examine the fan if there are any waggles damages or adhes...

Страница 22: ...he log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used t...

Страница 23: ... E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdo...

Страница 24: ...break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor err...

Страница 25: ...01 Comp 1 side 02 Comp 2 side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detec...

Страница 26: ... Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch alarm...

Страница 27: ...United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMD AP0074SPH E MMD AP0094SPH E MMD AP0124SPH E MMD AP0154SPH E MMD AP0184SPH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of t...

Страница 28: ... air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards...

Страница 29: ...IGH STATIC 2 0003 F HIGH STATIC 3 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F HIGH STATIC 1 0001 F HIGH STATIC 2 0003 F HIGH STATIC 3 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F HIGH STATIC 1 0001 F HIGH STATIC 2 0003 F HIGH STATIC 3 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in IT...

Страница 30: ...EH99879399 00EH99879301_01EN book Page 33 Tuesday March 15 2011 8 42 PM ...

Отзывы: