Toshiba MMD-AP0074SPH-E Скачать руководство пользователя страница 15

SMMS Slim Duct Type

Installation Manual

EN

SMMS Slim Duct Type

Installation Manual

– 14 –

8

Electrical Connection

WARNING

Use the specified wires for wiring connect the 
terminals. Securely fix them to prevent external 
forces applied to the terminals from affecting the 
terminals.

Incomplete connection or fixation may cause a fire or 
other trouble.

Connect earth wire. (grounding work)

Incomplete grounding cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, 
lightning conductor or telephone earth wires.

Appliance shall be installed in accordance with 
national wiring regulations.

Capacity shortage of power circuit or incomplete 
installation may cause an electric shock or a fire.

CAUTION

• If incorrect / incomplete wiring is carried out, it will 

cause an electrical fire or smoke.

• Install an earth leakage breaker that is not tripped by 

shock waves.

 

If an earth leakage breaker is not installed, an electric 
shock may be caused.

• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and 

inner insulator of power and inter-connecting wires 
when peeling them.

• Use the power cord and Inter-connecting wire of 

specified thickness, type, and protective devices 
required.

• Do not connect 220 V – 240 V power to the terminal 

blocks (

) for control wiring. (Otherwise, 

the system will fail.)

• Do not damage or scratch the conductive core and 

inner insulator of power and inter-connecting wires 
when peeling them.

• Perform the electric wiring so that it does not come to 

contact with the high-temperature part of the pipe.

 

The coating may melt resulting in an accident.

REQUIREMENT

• For power supply wiring, strictly conform to the Local 

Regulation in each country.

• For wiring of power supply of the outdoor units, follow 

the Installation Manual of each outdoor unit.

• Perform the electric wiring so that it does not come to 

contact with the high-temperature part of the pipe.The 
coating may melt resulting in an accident.

• After connecting wires to the terminal blocks, provide 

a trap and fix wires with the cord clamp.

• Run the refrigerant piping line and control wiring line in 

the same line.

• Do not turn on the power of the indoor unit until 

vacuuming of the refrigerant pipes completes.

„

Power supply wire and 
communication wires 
specifications

Power supply wire and communication wires are 
procured locally.
For the power supply specifications, follow to the table 
below. If capacity is little, it is dangerous because 
overheat or burnout may be caused.
For specifications of the power capacity of the outdoor 
unit and the power supply wires, refer to the Installation 
Manual attached to the outdoor unit.

Indoor unit power supply

• For the power supply of the indoor unit, prepare the 

exclusive power supply separated from that of the 
outdoor unit.

• Arrange the power supply, circuit breaker, and main 

switch of the indoor unit connected to the same 
outdoor unit so that they are commonly used.

• Power supply wire specification: Cable 3-core 2.5 

mm², 

in conformity with Design 60245 IEC 57

.

U

1

U

2

A

B

Power supply

Control wiring, Central controller wiring

• 2-core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central 

controller wiring.

• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and 

outdoor units added with the central control system wire length.

Communication line

Remote controller wiring

• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.

CAUTION

The remote controller wire (Communication line) and AC 220 – 240 V wires cannot be parallel to contact 

each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control 

system due to noise or other factor.

Power supply

220 V – 240 V ~, 50 Hz

220 V ~, 60 Hz

Power supply switch / circuit breaker or power supply wiring / fuse rating for indoor units should be selected by the 

accumulated total current values of the indoor units.

Power supply wiring

Below 50 m

2.5 mm

2

Control wiring between indoor units, and 

outdoor unit (2-core shield wire)

Wire size

(Up to 1000 m) 1.25 mm²

(Up to 2000 m) 2.0 mm²

Central control line wiring (2-core shield 

wire)

Wire size

(Up to 1000 m) 1.25 mm²

(Up to 2000 m) 2.0 mm²

Remote controller wiring, remote controller inter-unit 

wiring

Wire size: 0.5 mm² to 2.0 mm²

Total wire length of remote controller wiring and remote 

controller inter-unit wiring = L + L1 + L2 + … Ln

In case of wired type only

Up to 500 m

In case of wireless type 

included

Up to 400 m

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 200 m

L1

L

L2

Ln

Indoor unit

Remote controller inter-unit wiring

Indoor unit

Indoor unit

Indoor unit

Remote

controller

(Max. 8 units)

Remote 

controller 

wiring

27-EN

28-EN

+00EH99879301_01EN.book  Page 14  Tuesday, March 15, 2011  8:42 PM

Содержание MMD-AP0074SPH-E

Страница 1: ...sh Indoor Unit Model name Slim Duct Type MMD AP0074SPH E MMD AP0094SPH E MMD AP0124SPH E MMD AP0154SPH E MMD AP0184SPH E AIR CONDITIONER MULTI TYPE Installation Manual 00EH99879301_01EN book Page 1 Tuesday March 15 2011 8 42 PM ...

Страница 2: ... piping work involved in installation relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructe...

Страница 3: ...pair of outdoor unit Gloves to provide protection for electricians and from heat Warning indications on the air conditioner unit Warning indication Description WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit before the servicing CAUTION High temperature parts You might get burn...

Страница 4: ...ance in a place where it is directly exposed to the wind of air conditioner otherwise it may cause imperfect combustion Installation Suction duct length must be longer than 850 mm When the indoor unit is to be suspended the designated hanging bolts M10 or W3 8 and nuts M10 or W3 8 must be used Install the air conditioner securely in a location where the base can sustain the weight adequately If th...

Страница 5: ...er It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire electric shocks injury water leakage noise and or vibration may result When carrying out the pump down work shut down the compressor before disconnecting the refrigerant pipe Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or oth...

Страница 6: ... trouble in the air conditioner or noise may adversely affect the equipment s operation Locations where there is anything under the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inv...

Страница 7: ...erm setup of the filter sign Notification of filter cleaning of the remote controller can be changed according to the condition of installation For setup method refer to Filter sign setting in the Applicable controls of this Manual Remove the cover plate and then fix it to the bottom surface Do surely hooking to the main unit Main unit after remover Air filter Main unit Air filter Force Remove the...

Страница 8: ... 103 21 20 40 359 372 422 502 19 21 21 163 Ø 9 2 31 Installation of hanging bolt Consider the piping wiring after the unit is hung to determine the location of the indoor unit installation and orientation After the location of the indoor unit installation has been determined install hanging bolts For the dimensions of the hanging bolt pitches refer to the external view When a ceiling already exist...

Страница 9: ...10 Nut W3 8 or M10 8 m or less 5 Drain Piping CAUTION Following the Installation Manual perform the drain piping work so that water is properly drained and apply a heat insulation so as not to cause a dew drop Inappropriate piping work may result in water leakage in the room and wet of furniture Piping Heat insulating material Require the following materials for piping and heat insulating at site ...

Страница 10: ...e and hose band for connecting the drain hose to the clear drain socket If applying the adhesive socket will be damaged and cause water leakage Align the attached hose band to the end of hose set the tightening position upward and then tighten it Flexible hose Accessory Socket for VP25 vinyl chloride pipe locally procured Drain pipe connecting port Hard socket VP25 vinyl chloride pipe locally proc...

Страница 11: ...ts and seams of the heat insulator upward to avoid water leakage Wrap the attached heat insulator seamlessly from the surface of the indoor unit Flexible hose Hose band Attached heat insulator Heat insulator to be procured locally Hard vinyl chloride pipe 6 Duct Design Arrangement Unit mm Referring to the following dimensions manufacture duct at the local site Under air intake Back air intake 805 ...

Страница 12: ...lete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop Flange locally procured Aluminum tape locally procured Aluminum tape locally procured Under surface Cover a screw Heat insulator with sticking material 100 mm width locally procured Aluminum tape locally procured Air discharge side Indoor unit Air intake side Connect a duct to the inside of...

Страница 13: ...static pressure 20 Pa External static pressure Pa Air Volume m3 h Filter attached AP007 AP009 AP012 AP015 AP018 0 10 20 30 40 50 60 300 400 500 600 700 Standard air volume 540 m3 h Upper limit of external static pressure 50 Pa High 50 Pa Lower limit of externa static pressure 50 Pa Low 50 Pa High 20 Pa Low 35 Pa Low 20 Pa High 10 Pa Low 10 Pa Upper limit of external static pressure 35 Pa Upper lim...

Страница 14: ...0 to 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9 19 7 Work using double spanner Use the tightening torque levels as listed in the table below Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Therefore using a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units...

Страница 15: ...e power supply specifications follow to the table below If capacity is little it is dangerous because overheat or burnout may be caused For specifications of the power capacity of the outdoor unit and the power supply wires refer to the Installation Manual attached to the outdoor unit Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from...

Страница 16: ...Pass the wires through the bushing of wire connection holes of the indoor unit Keep a margin Approx 100 mm on a wire to hang down the electrical control box at servicing or other purpose The low voltage circuit is provided for the remote controller Do not connect the high voltage circuit Before remove the electrical control box cover remove the cover plate and air filter Remove the cover of the el...

Страница 17: ...ange the indoor unit settings The settings are changed by operating the wired remote controller The settings cannot be changed using only a wireless remote controller simple remote controller or group control remote controller by itself so install a wired remote controller separately as well Basic procedure for changing settings Change the settings while the air conditioner is not working Stop the...

Страница 18: ... 6 Specify 5d to the CODE No in procedure 3 For the SET DATA of procedure 4 select a SET DATA of the external static pressure to be set up from the following table Change on wired remote controller With a remote controller less system group control Besides the switching method using the wired remote controller as a way to establish the external static pressure switching is also possible by changin...

Страница 19: ... Detection temperature shift value 0000 No shift 0001 1 C 0002 2 C Factory default 0003 3 C 0004 4 C 0005 5 C 0006 6 C SET DATA 0000 0001 Remotecontroller sensor Not used Factory default Used 10Test Run Before test run Before turning on the power supply carry out the following procedure 1 By using 500 V megger check that resistance of 1 MΩ or more exists between the terminal block L to N and the e...

Страница 20: ...n finished stop the air conditioner from the wireless remote controller and return Dip switch of the receiver section as before A 60 minutes timer clearing function is attached to the receiver section in order to prevent a continuous test operation Small screw Nameplate Notch M4 25 screw 2 pieces Spacer Receiver unit 11Maintenance Daily maintenance Cleaning of air filter If is displayed on the rem...

Страница 21: ... service person Maintenance List Parts Inspection method Heat exchanger Access from inspection opening and remove the access panel Examine the heat exchanger if there is any clogging or damages Fan motor Access from inspection opening and check if any abnormal noise can be heard Fan Access from inspection opening and remove the access panel Examine the fan if there are any waggles damages or adhes...

Страница 22: ...he log can be confirmed from both operating status and stop status 1 When and buttons are pushed simultaneously for 4 seconds or more the following display appears If is displayed the mode enters in the error log mode 01 Order of error log is displayed in CODE No Error code is displayed in CHECK Indoor unit address in which an error occurred is displayed in Unit No 2 Every pushing of button used t...

Страница 23: ... E03 97 Communication error between indoor unit and remote controller Detected at indoor unit side Indoor unit E04 04 Communication circuit error between indoor outdoor unit Detected at indoor unit side Indoor unit E06 E06 No of indoor units in which sensor has been normally received 04 Decrease of No of indoor units I F E07 Communication circuit error between indoor outdoor unit Detected at outdo...

Страница 24: ...break down IPDU H02 H02 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 1d Compressor trouble lock IPDU H03 H03 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side 17 Current detect circuit system error IPDU H04 H04 44 Comp 1 case thermo operation I F H05 H05 TD1 sensor miswiring I F H06 H06 20 Low pressure protective operation I F H07 H07 d7 Oil level down detective protection I F H08 H08 01 TK1 sensor err...

Страница 25: ...01 Comp 1 side 02 Comp 2 side 03 Comp 3 side AF ALT Phase missing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detec...

Страница 26: ... Comp 3 Fan Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash C05 Sending error in TCC LINK central control device TCC LINK C06 Receiving error in TCC LINK central control device TCC LINK C12 Batch alarm...

Страница 27: ...United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMD AP0074SPH E MMD AP0094SPH E MMD AP0124SPH E MMD AP0154SPH E MMD AP0184SPH E Commercial name Super Modular Multi System Air Conditioner Super Heat Recovery Multi System Air Conditioner Mini Super Modular Multi System Air Conditioner MiNi SMMS series Complies with the provisions of t...

Страница 28: ... air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards...

Страница 29: ...IGH STATIC 2 0003 F HIGH STATIC 3 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F HIGH STATIC 1 0001 F HIGH STATIC 2 0003 F HIGH STATIC 3 0006 External static pressure CODE NO 5d F NO CHANGE F STANDARD 0000 F HIGH STATIC 1 0001 F HIGH STATIC 2 0003 F HIGH STATIC 3 0006 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in IT...

Страница 30: ...EH99879399 00EH99879301_01EN book Page 33 Tuesday March 15 2011 8 42 PM ...

Отзывы: