Installation Manual
– 36 –
EN
Finishing operation
1
Set the rotary switches on the interface P.C. board of the outdoor unit back: SW01 to [1], SW02 to [1] and
SW03 to [1].
<Collective test run>
Start operation
1
Set the rotary switches on the interface P.C. board of the outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
2
Push and hold SW04 for more than 2 seconds.
NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display
[A]
[U1]
[B]
[ ]
7-segment display
[A]
[C ]
[H ]
[B]
[ ]
[ ]
7-segment display
[A]
[C ]
[H ]
[B]
[ - C ]
[ - H ]
Stop operation
1
Set the rotary switches on the interface P.C. board of the outdoor unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].