Wire the remote controller
Wiring diagram
Terminal block for the remote control wiring on the indoor unit
Requirements for wiring of group control
• To make wiring of group control for indoor units of 4-way cassette type and other types, set the 4-way cassette
type as the header unit; otherwise, some settings such as the individual louver setting are not available.
• To make wiring of group control for the indoor unit with the automatic grille-up / down function and the one without
the function, set the indoor unit with the automatic grille-up / down function as the header unit; otherwise, the
automatic grille-up / down function is not available.
Requirements for installing two remote controllers
In the dual remote controller system, one or more units are operated from two remote controllers. (Up to two remote
controllers can be installed.)
Set the follower remote controller
Set from “6. Header/follower” in “10. Initial setting” on the MENU screen.
For details, refer to the page 16.
Install the remote controllers
For the dual remote controller system, install the remote controllers as follows:
1
Set one remote controller as the header remote controller.
(The remote controllers are set as “Header remote controller” as factory default.)
2
When the dual remote controller system is installed by using this remote controller (RBC-
AMS51E-EN) with the other type of remote controller, set this remote controller as the header
remote controller.
Remote control wiring (procured locally)
Terminal block for
the remote control
wiring
Remote controller
* Terminals of A and B
have no polarity.
* Use wire of 0.5 mm
2
to 2.0 mm
2
.
* A crimp-style terminal cannot be used.
+00EH97062301.book Page 7 Thursday, March 17, 2011 10:51 AM