HX7+ ASD Installation and Operation Manual
HX7+ ASD Characteristics
Over-Current Protection
Each
HX7+ ASD
model was designed for a specified operating power range. The HX7+ ASD will incur a
trip if the design specifications are exceeded.
However, the HX7+ ASD may be operated at 120% of the specified output-current range for a limited
amount of time as indicated in the section titled
Voltage/Current and Thermal Specifications on pg. 230
Also, the
) may be adjusted to help with nuisance over-current trips.
When using the HX7+ ASD for an application that controls a motor which is rated significantly less than
the maximum current rating of the HX7+ ASD, the over-current limit setting will have to be changed to
match the application. See
Electronic Thermal Protection #1
for further information on this ASD/motor
configuration.
HX7+ ASD Capacity
The
HX7+ ASD
must not be used with a motor that has a significantly larger capacity, even if the motor is
operated under a small load. An HX7+ ASD being used in this way will be susceptible to a high-output
peak current which may result in nuisance tripping.
Do not apply a level of input voltage to an HX7+ ASD that is beyond that which the HX7+ ASD is rated.
The input voltage may be stepped down when required with the use of a step-down transformer or some
other type of voltage reduction system.
Using Vector Control
Using
Vector Control
enables the system to produce very high torque over the entire operating range
even at extremely low speeds.
Vector Control
may be used with or without feedback. However, using
feedback increases the speed accuracy for applications requiring precise speed control. Enabling the
Automatic Energy Savings
further increases the efficiency of the
HX7+ ASD
while maintaining its
robust performance.
Vector Control
is not capable of operating multiple motors connected in parallel.
See
for further information on using
Vector Control
.
Local
|
Remote Operation
While running in the
Local
mode at a non-zero speed, if the RJ45 connector is removed from the
keypad
,
the
HX7+ ASD
remains in the
Local
mode running at the last commanded speed even though the
Local|Remote
LED is off. The HX7+ ASD output remains at the frequency of the
field at the time of the disconnect for the duration of the disconnect.
Once reinserted, the reference frequency goes to zero hz.
To prevent this condition, before disconnecting the RJ45 connector, ensure that the HX7+ ASD is off.
CAUTION
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...