HX7+ ASD Installation and Operation Manual
Electronic Thermal Protection #1
Program
Motor Parameters
Motor Set #1
The
Motor #1 Electronic Thermal Protection
parameter specifies the motor
overload current level for motor set #1. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to
Amps
or it may be set
as a percentage of the ASD rating. The name-plated FLA of the motor may be
entered directly when
Amps
is selected as the unit of measurement (see
to
change the display unit).
Electronic Thermal Protection
settings
(#1 – #4) will be displayed in
Amps
if
the keypad display units are set to
V/A
rather than
%
.
Direct Access Number — F600
Parameter Type —
Numerical
Factory Default —
100.0
Changeable During Run —
Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Over-Current Stall Level
Program
Protection
Stall
This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent a trip. The over-current level is entered as a
percentage of the maximum rating of the drive.
Note:
Parameter
(Soft Stall) must be enabled to use this feature.
Direct Access Number — F601
Parameter Type —
Numerical
Factory Default — (ASD dependent)
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 200.0
Units — %
Trip Save at Power Down Enable
Program
Protection
Trip Settings
This parameter
Enables/Disables
the
Trip Save at Power Down
setting. When
enabled, this feature logs the trip event and retains the trip information when the
system powers down. The trip information may be viewed from the
Monitor
screen.
When disabled, the trip information will be cleared when the system powers
down.
Settings:
0 — Disabled
1 — Enabled (box checked)
Direct Access Number — F602
Parameter Type —
Check Box
Factory Default —
Disabled
Changeable During Run —
No
Emergency Off Mode Settings
Program
Protection
Emergency Off
This parameter determines the method used to stop the motor in the event that
an
Emergency Off
command is received and the system is configured to use
this feature.
This setting may also be associated with the
FL
terminals to allow the
FL
relay
to change states when an
EOFF
condition occurs by setting the
FL
terminal to
Fault FL (all)
).
Note:
A supplemental emergency stopping system should be used with
the ASD. Emergency stopping should not be a task of the ASD
alone.
Settings:
0 — Coast Stop
1 — Deceleration Stop
2 — DC Injection Braking Stop
Direct Access Number — F603
Parameter Type —
Selection List
Factory Default —
Coast Stop
Changeable During Run —
No
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...