HX7+ ASD Installation and Operation Manual
VI/II Speed Frequency #1
Program
Frequency Setting
Speed Reference Setpoints
VI/II
This parameter is used to set the gain and bias of the
VI/II
input terminal when
the
VI/II
terminal is used as the control input while operating in the
Speed
Control
mode.
See
VI/II Speed Reference #1
) for further information on this setting.
This parameter sets
VI/II Speed Frequency #1
and is the frequency that is
associated with the setting of
VI/II Speed Reference #1
while operating in the
Speed Control
mode.
Direct Access Number — F202
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — 0.0
Maximum — Max. Freq. (
)
Units — Hz
VI/II Speed Reference #2
Program
Frequency Setting
Speed Reference Setpoints
VI/II
This parameter is used to set the gain and bias of the
VI/II
input terminal when
the
VI/II
terminal is used as the control input while operating in the
Speed
Control
mode or the
Torque Control
mode.
See
VI/II Speed Reference #1
for further information on this setting when
used for
Speed
control or
Torque
control.
This parameter sets the
VI/II
input level that is associated with
VI/II Speed
Frequency #2
while operating in the
Speed
control mode or is associated with
the
VI/II Torque Reference Setpoint #2
while operating in the
Torque
control
mode.
Direct Access Number — F203
Parameter Type —
Numerical
Factory Default —
100.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed Frequency #2
Program
Frequency Setting
Speed Reference Setpoints
VI/II
This parameter is used to set the gain and bias of the
VI/II
input terminal when
the
VI/II
terminal is used as the control input while operating in the
Speed
Control
mode.
See
VI/II Speed Reference #1
for further information on this setting when
used for
Speed
control.
This parameter sets the output frequency that is associated with
VI/II Speed
Reference #2
setting while operating in the
Speed
control mode.
Direct Access Number — F204
Parameter Type —
Numerical
Factory Default —
80.00
Changeable During Run —
Yes
Minimum — 0.0
Maximum —
Max. Freq.
Units — Hz
VI/II Torque Reference Setpoint #1
Program
Torque Setting
Setpoints
VI/II
This parameter is used to set the gain and bias of the
VI/II
input terminal when
the
VI/II
terminal is used as the control input while operating in the
Torque
Control
mode.
This is accomplished by establishing an associated
V/f
output pattern for a
given
VI/II
input level.
See
VI/II Speed Reference #1
for further information on this setting.
This parameter sets
VI/II
Torque Reference Setpoint #1
and is the output
torque value that is associated with the setting of
VI/II Speed Reference #1
while operating in the
Torque
control mode.
Direct Access Number — F205
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Содержание HX7+ ASD
Страница 1: ...HX7 ASD Install Op Manual TOSHIBA HX7 ASD INSTALLATION OPERATION MANUAL DN 67017 001 February 2014 ...
Страница 2: ...DN 67017 001 February 2014 HX7 ASD Installation Operation Manual ...
Страница 219: ...210 HX7 ASD Installation and Operation Manual Figure 27 66 200 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 220: ...HX7 ASD Installation and Operation Manual 211 Figure 28 260 518 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 221: ...212 HX7 ASD Installation and Operation Manual Figure 29 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 222: ...HX7 ASD Installation and Operation Manual 213 Figure 30 1200 1500 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 223: ...214 HX7 ASD Installation and Operation Manual Figure 31 66 200 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 224: ...HX7 ASD Installation and Operation Manual 215 Figure 32 260 518 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 225: ...216 HX7 ASD Installation and Operation Manual Figure 33 518 1000 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 226: ...HX7 ASD Installation and Operation Manual 217 Figure 34 1200 1500 kVA Non Sine Wave NEMA 3R Enclosure ...
Страница 227: ...218 HX7 ASD Installation and Operation Manual Figure 35 200 kVA Sine Wave NEMA 1 Enclosure ...
Страница 228: ...HX7 ASD Installation and Operation Manual 219 Figure 36 260 518 kVA Sine Wave NEMA 1 Enclosure ...
Страница 229: ...220 HX7 ASD Installation and Operation Manual Figure 37 518 1000 kVA Non Sine Wave NEMA 1 Enclosure ...
Страница 230: ...HX7 ASD Installation and Operation Manual 221 Figure 38 932 1500 kVA Sine Wave NEMA 1 Enclosure ...
Страница 231: ...222 HX7 ASD Installation and Operation Manual Figure 39 200 kVA Sine Wave NEMA 3R Enclosure ...
Страница 232: ...HX7 ASD Installation and Operation Manual 223 Figure 40 260 518 kVA Sine Wave NEMA 3R Enclosure ...
Страница 233: ...224 HX7 ASD Installation and Operation Manual Figure 41 518 1000 kVA Sine Wave NEMA 3R Enclosure ...
Страница 234: ...HX7 ASD Installation and Operation Manual 225 Figure 42 932 1500 kVA Sine Wave NEMA 3R Enclosure ...
Страница 235: ...226 HX7 ASD Installation and Operation Manual Figure 43 66 163 kVA 18 Pulse Enclosure ...
Страница 236: ...HX7 ASD Installation and Operation Manual 227 Figure 44 200 kVA 18 Pulse Enclosure ...
Страница 237: ...228 HX7 ASD Installation and Operation Manual Figure 45 260 518 kVA 18 Pulse Enclosure ...
Страница 238: ...HX7 ASD Installation and Operation Manual 229 Figure 46 518 700 kVA 18 Pulse Enclosure ...