6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 650 -
*Note: The OPTIM function can run on either “the SBO mode” or “the DIR mode” using a
signal “ctlmodel” when the communication is carried out in the IEC61850; thus,
mapping is required for the IEC61850 communication.
(ii)
Output signal required to map
The OPTIM function can issue a “Select success” signal at the output point
“OPTR01_NSD_CSF”, when the OPTIM function can decide that the input signal “Select
command (Reset)” is true. If the OPTIM function decides that the “Select command (Reset)” is
not true, the OPTIM function returns to the “Wait for a command” stage.
(iii)
Select condition
Figure 4.4-6 shows the select condition logic in the OPTIM function.
Select condition
OPTIM function (Function ID: 529001)
To selection logic
Control hierarchy (e.g. 43RL) (PLC connection point) *5
IED serious error detected
[
OPTR1_EN
]
On
Users must setup this condition correctly
Function
“Automatic sequence control” is in progress
CBK_STATE
Command blocking
*
1
Double Command Blocking detected
*
2
Other devices traveling detected
*
3
DCB RCV OR
Traveling OR
ASEQ_MULTI_SEL
OPTR01_CTRL_RIGHT
529001 820C01ED50
SERI_ERR
&
&
1
≥
Unmatched condition detected *4
Figure 4.4-6 Select condition logic in the OPTIM function
*6
*1
Note:
The “command blocking” disables any operation except for itself: the
“command blocking” is stated with “CBK” in a software controller (SOFTSW). The
IEC61850 defines the “command blocking” as “CmdBlk”. For more information on
CBK, see Chapter
Control and monitoring application: Software switch control
function. See the signal “CBK_STATE” of Table 4.4-2.
*2
Note:
“Double Command Blocking (DCB)” is operation philosophy in the common
control function (CMNCTRL). It can be used to protect the substation. The user
should program it using the GR-TIEMS. The DCB operating signal is denoted as
“DCB RCV_OR in Table 4.4-2. For more information, see Chapter
Control and
monitoring application: Common controls.
*3
Note:
If events “device-travelling” are detected in the CMNCTRL function, we can
see that some statuses of the devices are being changed by other operators. Thus,
the IED should stop any operation while the events are being detected. The
detecting signal is denoted by “Traveling OR” in Table 4.4-2.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......