6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 1143 -
LAN operation
11.2.1
LAN address (IP address)
The IED can have the communication with “Transmission Control Protocol/Internet Protocol
(TCP/IP)”. The user can set the information about IP addresses and other TCP/IP. Table 11.2-1
shows the setting items provided for the LAN†.
These setting values have been included in the CID file of the IEC61850. When the IED starts
up and if values except for the 0.0.0.0 values or default are set in the CID file, the CID
information is taken into the IED.
As the setting values have been included in the CID file, the user can define these values with
the engineering tool (GR-TIEMS). If the user wishes to modify those and the IEC61850 is used
to communicate, the user can change those with the GR-TIEMS. The user is required to write
both of setting values and IEC61850-CID file into the IED.
Table 11.2-1 TCP/IP settings at LAN modules
Ports
Setting items
Range
Setting meaning
Default value
Port A
at C11
IPADDRESS1
0.0.0.0–255.255.255.255
First IP address
192.l68.1.11
SUBNETMASK1
0.0.0.0–255.255.255.255
Subnet mask
255.255.255.0
GATEWAY1
0.0.0.0–255.255.255.255
Default gateway
192.168.1.1
Port B
at C12
IPADDRESS2‡
0.0.0.0–255.255.255.255
Second IP address
192.l68.1.12
SUBNETMASK2‡
0.0.0.0–255.255.255.255
Subnet mask
255.255.255.0
GATEWAY2‡
0.0.0.0–255.255.255.255
Default gateway
192.168.1.1
When the user wishes to change addresses, enter the new address into the IED using the LAN
setting sub-menu (Figure 11.2-1). The setting menu is provided for the user to change the
addresses‡.
LAN
10:48
1/6
IPADDRESS1
+
192.168.1.11
SUBNETMASK1
+
255.255.255.1
GATEWAY1
+
192.168.1.1
Figure 11.2-1 Local LAN setting menu (on IED screen)
†Note: For the location of the LAN communication modules, see Chapter
Technical
description: Signal processing and communication module.
‡Note: IP address setting is dependent on the selection of the communication protocols.
Содержание GR 200 Series
Страница 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Страница 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Страница 1369: ...6F2S1915 0 46 GRZ200 Soft 031 032 1348 Unit mm Panel cut out for 1 2 case size Figure 2 2 3 Panel cutout figure 1 2 size case ...
Страница 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Страница 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Страница 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Страница 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Страница 1520: ...6F2S1915 0 46 GRZ200 Soft 031 032 1499 Appendix 9 Matrix between VCT terminals and relay applications ...
Страница 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Страница 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Страница 1563: ......